DR4300 Circular Chart Recorder Product Manual
Configuration, Startup, and Operation
Parameter
Definition
ALARM 1 SETPOINT 1 STATE—Select whether you
want the alarm type chosen in prompt "A1S1TY" to alarm
high or low.
HI ALARM—Relay coil is de-energized when the PV is
above the setpoint.
LO ALARM—Relay coil is de-energized when the PV is
below the setpoint.
ALARM 1 SETPOINT 2 STATE—Select whether you
want the alarm type chosen in prompt "A1S2TY" to alarm
high or low.
HI ALARM—Relay coil is de-energized when the PV is
above the setpoint.
LO ALARM—Relay coil is de-energized when the PV is
below the setpoint.
ALARM 1 HYSTERESIS—This is an adjustable
hysteresis provided on alarm 1 that activates at exactly
the alarm setpoint when the alarm is OFF. When the
alarm is ON, it will not deactivate until the variable is
away from the alarm setpoint by a value equal to A1
HYS. Configure the hysteresis as a percent of input
range span.
ALARM 2 SETPOINT 1 TYPE—Select what you want
Setpoint 1 of Alarm 2 to represent. The selections are the
same as "A1S1TY".
ALARM 2 SETPOINT 2 TYPE—Select what you want
Setpoint 2 of Alarm 2 to represent. The selections are the
same as "A1S1TY".
ALARM 2 SETPOINT 1 VALUE—This is the value at
which you want the alarm type chosen in prompt
"A2S1TY" to actuate. The appropriate value depends on
what the setpoint has been configured to represent.
ALARM 2 SETPOINT 2 VALUE—This is the value at
which you want the alarm type chosen in prompt
"A2S2TY" to actuate. The appropriate value depends on
what the setpoint has been configured to represent.
ALARM 2 SETPOINT 1 STATE—Select whether you
want the alarm type chosen in prompt "A2S1TY" to alarm
high or low.
HI ALARM—Relay coil is de-energized when the PV is
above the setpoint.
LO ALARM—Relay coil is de-energized when the PV is
below the setpoint.
ALARM 2 SET POINT 2 STATE—Select whether you
want the alarm type chosen in prompt "A2S2TY" to alarm
high or low.
HI ALARM—Relay coil is de-energized when the PV is
above the setpoint.
LO ALARM—Relay coil is de-energized when the PV is
below the setpoint.
of Recorder with Display
107