Advertisement

5.4.4 RTD (Resistance Temperature Detector) Inputs

Refer to Figure 5-4 and wire the recorder according to the procedure given in Table 5-7.
Step
Connect the copper wire to the calibration source (see Table 5-3).
1
2
Connect the other end of the copper wire to the TB2 terminals on the printed circuit assembly
for the input channel being calibrated.
4/00

Table 5-7 Set Up Wiring Procedure for Calibrating RTD Inputs

Main PCA
Pen 2
TB1
Figure 5-4 Calibration Set Up Diagram for RTD Inputs
DR4300 Circular Chart Recorder Product Manual
Input and Output Calibration for Recorder with Display
Action
Main PCA
Pen 1
TB2
TB1
TB2
R
Decade box
Copper
wires
TB2
24093
-
+
149