8.3.2 View Status of Tests

Procedure
The status of self-diagnostic tests can be viewed using the procedure in Table 8-3.
Note that "FAILSF" is not a test. When "FAILSF YES" is displayed, it is an indication that the recorder is
using the value of the control set up group "FAILSF" parameter as the output value because the recorder
failed a self-test, or because the recorder detected an input failure while the input set up parameter
"BRNOUT" = "NONE".
See Table 8-4 for more information about self-diagnostics, and for recommended actions when a test fails.

Table 8-3 Procedure for Displaying the Results of Self-Diagnostics

Step
1
Select STATUS
set up Group
2
Read the status tests
results
4/00
Operation
Press
SET
UP
FUNC
DR4300 Circular Chart Recorder Product Manual
Troubleshooting and Pen Alignment
Action/Result
Until you see:
Upper Display
READ
Lower Display
STATUS
Until you see:
Upper Display
YES indicates
NO or YES
a failure
Lower Display
FAILSF
• Successive presses of the FUNC key will display
the results of the status tests (PASS or FAIL) in the
following order:
RAMTST
CFGTST
CALTST
• Identify the problem and correct the failure as
shown in Table 8-4.