DR4300 Circular Chart Recorder
4.5.2.3 Changing the Control Setpoint
Procedure
The recorder can be set up for control on pen channel 1 and/or 2 as described earlier in this section. Follow
the procedure in Table 4-30 to change the control setpoints.
Step
1
Select setpoint for
the pen 1 channel
(input 1).
Select setpoint for
2
pen 2 (input 2)
3
Return to input 1
parameters for
display
If remote switch is set to SP2 then DISP will allow setting of second setpoint (S2).
134

Table 4-30 Procedure for Changing the Control Setpoints

Operation
Press
DISP
or
FUNC
DISP
or
FUNC
DR4300 Circular Chart Recorder Product Manual
Action/Result
until you see:.
Upper Display
shows the input value.
Lower Display
shows SP and the setpoint
value for the selected channel.
to change the setpoint to the desired value.
Until "INP 2" indicator lights.
until you see:.
Upper Display
shows the input value.
Lower Display
shows S2 and the second
setpoint for the selected
channel.
to change the setpoint to the desired value.
to light "INP 1" indicator
4/00