Table 4-31 Procedure For Displaying Or Changing The Alarm Setpoints - Honeywell DR4300 Product Manual

Circular chart recorder
Hide thumbs Also See for DR4300:
Table of Contents

Advertisement

4.5.2.4 Viewing and Changing Alarm Setpoints
Introduction
If the recorder hardware supports outputs, one or both relays can be used for alarming. An alarm is an
indication that an event specified during configuration (process variable, for example) has exceeded one or
more alarm limits. There are two alarms available for each pen (assuming no relay is being used for
control). Each alarm has two setpoints. There are two alarm output selections, high and low. During
configuration, each alarm setpoint is configured to alarm either high or low.
The alarm setpoints can be changed by the operator if the alarm parameters are not locked (see Subsection
4.3.19). If a recorder output is being used for control, that output is not available as an alarm and the
prompts will not appear.
Procedure
The procedure for displaying and changing the alarm setpoints is listed in Table 4-31.

Table 4-31 Procedure for Displaying or Changing the Alarm Setpoints

Step
Access the Alarm Set
1
Up group
Access the Alarm
2
Setpoint Values
3
Return to normal
operation
4/00
Operation
Press
SET
UP
FUNC
or
DISP
DR4300 Circular Chart Recorder Product Manual
Configuration, Startup, and Operation
Action/Result
Until you see:
Upper Display
SET
Lower Display
ALARMS
Until you display the desired alarm setpoint and its
value. Their order of appearance is shown below.
Upper Display
The alarm setpoint
value
Lower Display
A1S1 VA =
(Alarm 1, Setpoint 1 value)
A1S2 VA =
(Alarm 1, Setpoint 2 value)
A2S1 VA =
(Alarm 2, Setpoint 1 value)
A2S2 VA =
(Alarm 2, Setpoint 2 value)
Change any alarm setpoint value you select in the
upper display.
Returns to normal operation.