Det-Tronics X5200 Instructions Manual page 26

Uvir flame detector
Hide thumbs Also See for X5200:
Table of Contents

Advertisement

REspONsE CHARACtERIstICs IN tHE pREsENCE OF FALsE ALARM sOuRCEs:
High sensitivity, Hi Arc, tDsA On, Quick Fire Off
False Alarm source
Sunlight, direct, modulated/unmodulated
Sunlight, reflected, modulated/unmodulated
70 w sodium vapor lamp, unmodulated
70 w sodium vapor lamp, modulated
250 w mercury vapor lamp, unmodulated
250 w mercury vapor lamp, modulated
300 w incandescent lamp, unmodulated
300 w incandescent lamp, modulated
500 w shielded quartz halogen lamp, unmodulated
500 w shielded quartz halogen lamp, modulated
1500 w electric quartz heater, unmodulated
1500 w electric quartz heater, modulated
Two 34 w fluorescent lamps, unmodulated
Two 34 w fluorescent lamps, modulated
Arc welding
*Add 2 seconds for EQP Model.
FALsE ALARM IMMuNItY:
High sensitivity, Hi Arc, tDsA On, Quick Fire Off
False Alarm source
Sunlight, direct, reflected
Vibration
Arc welding
70 w sodium vapor lamp
250 w mercury vapor lamp
300 w incandescent lamp
500 w shielded quartz halogen lamp
1500 w electric quartz heater
Two 34 w fluorescent lamps
8.2
FM Approvals Description and performance Report – Continued
Distance
feet (m)
Distance
feet (m)
Fire source
2 inch dia Heptane
2 inch dia Heptane
5 (1.5)
2 inch dia Heptane
5 (1.5)
2 inch dia Heptane
5 (1.5)
2 inch dia Heptane
5 (1.5)
2 inch dia Heptane
5 (1.5)
2 inch dia Heptane
5 (1.5)
2 inch dia Heptane
5 (1.5)
2 inch dia Heptane
5 (1.5)
2 inch dia Heptane
10 (3)
2 inch dia Heptane
10 (3)
2 inch dia Heptane
3 (0.9)
2 inch dia Heptane
3 (0.9)
2 inch dia Heptane
15 (4.6)
2 inch dia Heptane
Modulated Response
No alarm
N/A
No alarm
15 (4.6)
No alarm
3 (0.9)
No alarm
3 (0.9)
No alarm
3 (0.9)
No alarm
3 (0.9)
No alarm
10 (3)
No alarm
3 (0.9)
No alarm
24
Distance
Average Response time
feet (m)
(seconds)*
10 (3)
< 30
10 (3)
< 30
5 (1.5)
3
5 (1.5)
3
5 (1.5)
2
5 (1.5)
3
5 (1.5)
4
5 (1.5)
3
5 (1.5)
2
5 (1.5)
2
5 (1.5)
3
3 (0.9)
11
10 (3)
3
10 (3)
5
5 (1.5)
N/A
unmodulated Response
No alarm
No alarm
No alarm
No alarm
No alarm
No alarm
No alarm
No alarm
No alarm
95-8546