Setting System Alarm Notifications - DPS Telecom NetGuardian 216T User Manual

Compact lan- and t1-wan-based alarm collector; web browser
Hide thumbs Also See for NetGuardian 216T:
Table of Contents

Advertisement

2.9

Setting System Alarm Notifications

Fig. 2.9.1. SNMP Traps and primary or secondary pager devices can be selected for each system alarm
The System Alarms screen allows you to individually set the notification method for each system alarm. See
Appendix A for system alarm point descriptions.
Use the following steps to configure your system alarm notification settings:
1. From the Edit menu select the System Alarms link (see Figure 2.9.1).
2. Check the Trap box to send an SNMP trap for that alarm point. Selecting the box will set that point to send a
SNMP trap; leaving the box blank will set that point to not send an SNMP trap.
3. Set the primary and secondary pagers with a pager ID from your defined pager list (see Section 2.5, "Setting
up Notification Methods" for more information).
Note: The NetGuardian will notify both the primary and the secondary notification device when point status
changes (both alarm and clear).
Under the Group column enter the appropriate point group ID (see Section 2.6, "Defining Point Groups)."
4.
5. Click Submit Data to save the configuration settings.