6 ACTUAL VALUES
f) FREQUENCY

PATH: ACTUAL VALUES
METERING
 FREQUENCY
 SRC 1
The metered frequency values are displayed in this menu. The "SRC 1" text will be replaced by whatever name was pro-
grammed by the user for the associated source (see
is measured via software-implemented zero-crossing detection of an AC signal. The signal is either a
SOURCE FREQUENCY
Clarke transformation of three-phase voltages or currents, auxiliary voltage, or ground current as per source configuration
(see the

SYSTEM SETUP
final frequency measurement is passed through a validation filter that eliminates false readings due to signal distortions and
transients.

PATH: ACTUAL VALUES
METERING
 TRACKING FREQUENCY
The tracking frequency is displayed here. The frequency is tracked based on the selection of the reference source with the
FREQUENCY AND PHASE REFERENCE
System section of chapter 5 for details.

PATH: ACTUAL VALUES
METERING
 FLEXELEMENT 1
The operating signals for the FlexElements are displayed in pu values using the following definitions of the base units.
Table 6–2: FLEXELEMENT BASE UNITS
BUS DIFFERENTIAL
RESTRAINING CURRENT
(Bus Diff Mag)
BUS DIFFERENTIAL
RESTRAINING CURRENT
(Bus Rest Mag)
DCmA
FREQUENCY
PHASE ANGLE
POWER FACTOR
RTDs
SOURCE CURRENT
SOURCE POWER
SOURCE VOLTAGE
GE Multilin

SOURCE SRC 1
SRC 1
FREQUENCY:
0.00 Hz
SETTINGS
settings). The signal used for frequency estimation is low-pass filtered. The
POWER SYSTEM


TRACKING FREQUENCY

TRACKING FREQUENCY:
60.00 Hz
setting in the
SETTINGS


FLEXELEMENTS

FLEXELEMENT 1
OpSig: 0.000 pu
I
= maximum primary RMS value of the +IN and –IN inputs
BASE
(CT primary for source currents, and bus reference primary current for bus differential currents)
I
= maximum primary RMS value of the +IN and – IN inputs
BASE
(CT primary for source currents, and bus reference primary current for bus differential currents)
BASE = maximum value of the
under the +IN and –IN inputs.
f
= 1 Hz
BASE
ϕ
= 360 degrees (see the UR angle referencing convention)
BASE
PF
= 1.00
BASE
BASE = 100°C
I
= maximum nominal primary RMS value of the +IN and –IN inputs
BASE
P
= maximum value of V
BASE
V
= maximum nominal primary RMS value of the +IN and –IN inputs
BASE
B30 Bus Differential System
FREQUENCY


SYSTEM SETUP
SIGNAL SOURCES


SYSTEM SETUP
POWER SYSTEM
FLEXELEMENT 1(8)
setting for the two transducers configured
DCMA INPUT MAX
× I
for the +IN and –IN inputs
BASE
BASE
6.3 METERING
).
6.3.5 TRACKING FREQUENCY
menu. See the Power
6.3.6 FLEXELEMENTS
6-17
6