CHAPTER 6: ACTUAL VALUES
If synchrocheck or a setting is "Disabled," the corresponding actual values menu item does not display.
6.4.5 Tracking frequency
ACTUAL VALUES METERING TRACKING FREQUENCY
TRACKING FREQUENCY
The tracking frequency displays here. The frequency is tracked based on the selection of the reference source with the
FREQUENCY AND PHASE REFERENCE
System section of chapter 5 for details.
6.4.6 Frequency rate of change
ACTUAL VALUES METERING FREQUENCY RATE OF CHANGE 1(4)
FREQUENCY RATE
OF CHANGE 1
The metered frequency rate of change for the frequency rate of change elements is shown here.
6.4.7 Frequency out-of-band accumulation
ACTUAL VALUES METERING FREQUENCY OOB ACCUMULATION
FREQUENCY OOB
ACCUMULATION
The frequency out-of-band accumulation metered values are displayed to the nearest percent as a ratio of the present
accumulation to the user-specified limit. Note that this value can be greater than 100%.
6.4.8 FlexElements
ACTUAL VALUES METERING FLEXELEMENTS FLEXELEMENT 1(16)
FLEXELEMENT 1
The operating signals for the FlexElements are displayed in pu values using the following definitions of the base units.
Table 6-2: FlexElement base units
Base unit
BREAKER ACC ARCING AMPS
(Brk X Acc Arc Amp A, B, and C)
BREAKER ARCING AMPS
(Brk X Arc Amp A, B, and C)
DCmA
G60 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL
SYNCHROCHECK 1 PROJ
SYNSCP D_PH: 0.0°
TRACKING FREQUENCY:
60.00 Hz
setting in the
SETTINGS SYSTEM SETUP POWER SYSTEM
FREQUENCY RATE OF
CHANGE1: 0.00 Hz/s
FREQUENCY OOB BAND 1
ACCUMULATION: 0.0%
FREQUENCY OOB BAND 2
ACCUMULATION: 0.0%
FREQUENCY OOB BAND 7
ACCUMULATION: 0.0%
FLEXELEMENT 1
OpSig:
0.000
Description
2
BASE = 2000 kA
× cycle
2
BASE = 1 kA
× cycle
BASE = maximum value of the DCMA INPUT MAX setting for the two transducers configured
under the +IN and –IN inputs.
METERING
menu. See the Power
6-23
6