CHAPTER 6: ACTUAL VALUES
If synchrocheck or a setting is "Disabled," the corresponding actual values menu item does not display.

6.4.5 Tracking frequency

ACTUAL VALUES  METERING  TRACKING FREQUENCY
 TRACKING FREQUENCY
The tracking frequency displays here. The frequency is tracked based on the selection of the reference source with the
FREQUENCY AND PHASE REFERENCE
System section of chapter 5 for details.

6.4.6 Frequency rate of change

ACTUAL VALUES  METERING  FREQUENCY RATE OF CHANGE 1(4)
 FREQUENCY RATE
 OF CHANGE 1
The metered frequency rate of change for the frequency rate of change elements is shown here.

6.4.7 Frequency out-of-band accumulation

ACTUAL VALUES  METERING  FREQUENCY OOB ACCUMULATION
 FREQUENCY OOB
 ACCUMULATION
The frequency out-of-band accumulation metered values are displayed to the nearest percent as a ratio of the present
accumulation to the user-specified limit. Note that this value can be greater than 100%.

6.4.8 FlexElements

ACTUAL VALUES  METERING  FLEXELEMENTS  FLEXELEMENT 1(16)
 FLEXELEMENT 1
The operating signals for the FlexElements are displayed in pu values using the following definitions of the base units.
Table 6-2: FlexElement base units
Base unit
BREAKER ACC ARCING AMPS
(Brk X Acc Arc Amp A, B, and C)
BREAKER ARCING AMPS
(Brk X Arc Amp A, B, and C)
DCmA
G60 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL
SYNCHROCHECK 1 PROJ
SYNSCP D_PH: 0.0°
TRACKING FREQUENCY:
60.00 Hz
setting in the
SETTINGS  SYSTEM SETUP  POWER SYSTEM
FREQUENCY RATE OF
CHANGE1: 0.00 Hz/s
FREQUENCY OOB BAND 1
ACCUMULATION: 0.0%
FREQUENCY OOB BAND 2
ACCUMULATION: 0.0%
FREQUENCY OOB BAND 7
ACCUMULATION: 0.0%
FLEXELEMENT 1
OpSig:
0.000
Description
2
BASE = 2000 kA
× cycle
2
BASE = 1 kA
× cycle
BASE = maximum value of the DCMA INPUT MAX setting for the two transducers configured
under the +IN and –IN inputs.
METERING
menu. See the Power
6-23