Teleprotection Channel Tests; Remaining Connection Status - GE B30 Instruction Manual

Ur series bus differential system protection relay
Hide thumbs Also See for B30:
Table of Contents

Advertisement

6.2 STATUS
PATH: ACTUAL VALUES
 TELEPROT CH TESTS
The status information for two channels is shown here.
CHANNEL 1 STATUS: This represents the receiver status of each channel. If the value is "OK", teleprotection is
enabled and data is being received from the remote terminal; If the value is "FAIL", teleprotection enabled and data is
not being received from the remote terminal. If "n/a", teleprotection is disabled.
CHANNEL 1 LOST PACKETS: Data is transmitted to the remote terminals in data packets at a rate of two packets per
cycle. The number of lost packets represents data packets lost in transmission; this count can be reset to 0 through the

COMMANDS
CLEAR RECORDS
VALIDITY OF CHANNEL CONFIGURATION: This value displays the current state of the communications channel
identification check, and hence validity. If a remote relay ID does not match the programmed ID at the local relay, the
"FAIL" message will be displayed. The "N/A" value appears if the local relay ID is set to a default value of "0", the chan-
nel is failed, or if the teleprotection inputs/outputs are not enabled.
6
PATH: ACTUAL VALUES
 COMM STATUS
 REMAINING CONNECT
These values specify the remaining number of TCP connections still available for each protocol. The display depends on
the options applicable to your device, for example the PMU entry does not display when not applicable. Each time a con-
nection is used, the remaining number of connections decrements. When released, the remaining number of connections
increments. If no connection is made over the specific protocol, the number equals the maximum number available for the
specific protocol.
For example, the maximum number of Modbus TCP connections is 4. Once an EnerVista session is opened on a computer
connected to the UR over Ethernet, the Modbus TCP status shows 3. If the EnerVista application is closed, the Modbus
TCP status shows 4.
— The number of IEC 61850 connections remaining.
MMS TCP
6-10

STATUS
TELEPROT CH TESTS
CHANNEL 1
STATUS: n/a
CHANNEL 1 LOST
MESSAGE
PACKETS:
CHANNEL 2
MESSAGE
STATUS: n/a
CHANNEL 2 LOST
MESSAGE
PACKETS:
VALIDITY OF CHANNEL
MESSAGE
CONFIGURATION: FAIL
menu.

STATUS
COMM STATUS REMAINING CONNECT
MMS TCP(max 5)
5
MODBUS TCP(max 4)
MESSAGE
4
DNP TCP (max 2)
MESSAGE
2
IEC-104 (max 2)
MESSAGE
2
B30 Bus Differential System

6.2.18 TELEPROTECTION CHANNEL TESTS

Range: n/a, FAIL, OK
Range: 1 to 65535 in steps of 1
1
Range: n/a, FAIL, OK
Range: 1 to 65535 in steps of 1
1
Range: n/a, FAIL, OK

6.2.19 REMAINING CONNECTION STATUS

Range: 0 to 5
Range: 0 to 4
Range: 0 to 2
Range: 0 to 2
6 ACTUAL VALUES
GE Multilin

Advertisement

Table of Contents
loading