GE B30 Instruction Manual page 144

Ur series bus differential system protection relay
Hide thumbs Also See for B30:
Table of Contents

Advertisement

5.2 PRODUCT SETUP
If a remote connection is established, local passcodes are not visible.
NOTE
REMOTE PASSWORDS
The remote password settings are visible only from a remote connection via the EnerVista UR Setup software.
Proper passwords are required to enable each command or setting level access.
To set the command or setting password:
1.
In the EnerVista software, navigate to Settings > Product Setup > Security menu item to open the remote password
settings window.
2.
Click the command or setting password Change button.
3.
Enter the new password in the New Password field. Requirements are outlined in the Password Requirements section
at the beginning of the chapter. When an original password has already been used, enter it in the Enter Password
field and click the Send Password to Device button.
4.
Re-enter the password in the Confirm Password field.
5.
Click the OK button. The password is checked to ensure that is meets requirements.
5
If you establish a local connection to the relay (serial), you cannot view remote passcodes.
NOTE
ACCESS SUPERVISION
PATH: SETTINGS
PRODUCT SETUP
 ACCESS
 SUPERVISION
The following access supervision settings are available.
INVALID ATTEMPTS BEFORE LOCKOUT: This setting specifies the number of times an incorrect password can be
entered within a three-minute time span before lockout occurs. When lockout occurs, the
REMOTE ACCESS DENIED
expiration of the lockout.
PASSWORD LOCKOUT DURATION: This setting specifies the time that the B30 will lockout password access after
the number of invalid password entries specified by the
The B30 provides a means to raise an alarm upon failed password entry. Should password verification fail while accessing
a password-protected level of the relay (either settings or commands), the
asserted. The operand can be programmed to raise an alarm via contact outputs or communications. This feature can be
used to protect against both unauthorized and accidental access attempts.
5-10

SECURITY
ACCESS SUPERVISION
 ACCESS LEVEL
 TIMEOUTS
INVALID ATTEMPTS
MESSAGE
BEFORE LOCKOUT: 3
PASSWORD LOCKOUT
MESSAGE
DURATION: 5 min
FlexLogic operands are set to "On". These operands are returned to the "Off" state upon
B30 Bus Differential System
Range: 2 to 5 in steps of 1
Range: 5 to 60 minutes in steps of 1
INVALID ATTEMPTS BEFORE LOCKOUT
UNAUTHORIZED ACCESS
5 SETTINGS
or
LOCAL ACCESS DENIED
setting has occurred.
FlexLogic operand is
GE Multilin