5 SETTINGS
The breaker configuration settings are shown below. Changes to these values take effect when the UR is restarted:
PATH: SETTINGS
PRODUCT SETUP
 XCBR
 CONFIGURATION
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
The XCBR1 ST.LOC OPERAND setting is used to inhibit 61850 control commands to close or open breaker through UR
Breaker Control element. See the Breaker Control element logic diagram for more information.
The CLEAR XCBR1 OpCnt setting allows clearing the breaker operating counter. As breakers operate by opening and
closing, the XCBR operating counter status attribute (OpCnt) increments with every operation. Frequent breaker operation
can result in very large OpCnt values over time. This setting allows the OpCnt to be reset to "0" for XCBR1.
GE Multilin


COMMUNICATIONS
IEC 61850 PROTOCOL
XCBR1 ST.LOC OPERAND
Off
XCBR6 ST.LOC OPERAND
Off
CLEAR XCBR1 OpCnt:
No
CLEAR XCBR6 OpCnt:
No
XCBR1 SYNCCHECK CLS:
Off
XCBR6 SYNCCHECK CLS:
Off
XCBR1 INTERLOCK OPN:
Off
XCBR6 INTERLOCK OPN:
Off
XCBR1 INTERLOCK CLS:
Off
XCBR6 INTERLOCK CLS:
Off
XCBR1 Pos ctlModel:
2
XCBR6 Pos ctlModel:
2
XCBR1 Pos
sboTimeout: 30 s
XCBR6 Pos
sboTimeout: 30 s
B30 Bus Differential System
5.2 PRODUCT SETUP

XCBR CONFIGURATION
Range: FlexLogic operand
Range: FlexLogic operand
Range: No, Yes
Range: No, Yes
Range: FlexLogic operand
Range: FlexLogic operand
Range: FlexLogic operand
Range: FlexLogic operand
Range: FlexLogic operand
Range: FlexLogic operand
Range: 0 to 4 (as per IEC 61850-7-3, ctlModel)
Range: 0 to 4 (as per IEC 61850-7-3, ctlModel)
Range: 2 to 60 seconds
Range: 2 to 60 seconds
5
5-53