5.2 PRODUCT SETUP
o) IEC 60870-5-104 PROTOCOL
PATH: SETTINGS
PRODUCT SETUP
 IEC 60870-5-104
 PROTOCOL
5
The B30 supports the IEC 60870-5-104 protocol. This protocol is enabled when the
MUNICATIONS
PROTOCOL
connected to a maximum of two masters (usually either an RTU or a SCADA master station). Since the B30 maintains two
sets of IEC 60870-5-104 data change buffers, no more than two masters should actively communicate with the B30 at one
time.
The
IEC ------- DEFAULT THRESHOLD
M_ME_NC_1 analog data. These settings group the B30 analog data into types: current, voltage, power, energy, and other.
Each setting represents the default threshold value for all M_ME_NC_1 analog points of that type. For example, to trigger
spontaneous responses from the B30 when any current values change by 15 A, the
ting should be set to 15. Note that these settings are the default values of the deadbands. P_ME_NC_1 (parameter of mea-
sured value, short floating point value) points can be used to change threshold values, from the default, for each individual
M_ME_NC_1 analog point. Whenever power is removed and re-applied to the B30, the default thresholds are in effect.
The
IEC REDUNDANCY
two simultaneous connections can be active at any given time.
: When set to 0, the change takes effect when the B30 is restarted.
IEC TCP PORT NUMBER
IEC COMMON ADDRESS OF ASDU
IEC CYCLIC DATA PERIOD
Do not set more than one protocol to the same TCP/UDP port number, as this results in unreliable operation of
those protocols.
NOTE
The B30 relay does not support power metering. As such, the
cable.
NOTE
5-56

COMMUNICATIONS
IEC TCP PORT
NUMBER: 2404
 IEC NETWORK
MESSAGE
 CLIENT ADDRESSES
IEC COMMON ADDRESS
MESSAGE
OF ASDU:
IEC CYCLIC DATA
MESSAGE
PERIOD:
IEC CURRENT DEFAULT
MESSAGE
THRESHOLD: 30000
IEC VOLTAGE DEFAULT
MESSAGE
THRESHOLD: 30000
IEC POWER DEFAULT
MESSAGE
THRESHOLD: 30000
IEC ENERGY DEFAULT
MESSAGE
THRESHOLD: 30000
IEC PF DEFAULT
MESSAGE
THRESHOLD: 1.00
IEC OTHER DEFAULT
MESSAGE
THRESHOLD: 30000
IEC REDUNDANCY
MESSAGE
ENABLED: No
setting is set to IEC 60870-5-104. The B30 can be used as an IEC 60870-5-104 slave device
settings are used to determine when to trigger spontaneous responses containing
setting decides whether multiple client connections are accepted or not. If redundancy is set to Yes,
: The change takes effect when the B30 is restarted.
: The change takes effect when the B30 is restarted.
B30 Bus Differential System

IEC 60870-5-104 PROTOCOL
Range: 0 to 65535 in steps of 1
Range: see sub-menu below
Range: 0 to 65535 in steps of 1
0
Range: 1 to 65535 s in steps of 1
60 s
Range: 0 to 65535 in steps of 1
Range: 0 to 65535 in steps of 1
Range: 0 to 65535 in steps of 1
Range: 0 to 65535 in steps of 1
Range: 0.00 to 1.00
Range: 0 to 65535 in steps of 1
Range: No, Yes
SETTINGS
IEC CURRENT DEFAULT THRESHOLD
IEC POWER DEFAULT THRESHOLD
5 SETTINGS

PRODUCT SETUP
COM-
set-
setting is not appli-