5 SETTINGS
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
The B30 supports the Distributed Network Protocol (DNP) version 3.0. DNP is enabled when the

SETUP
COMMUNICATIONS
nected to multiple DNP masters (usually an RTU or a SCADA master station). Since the B30 maintains two sets of DNP
data change buffers and connection information, two DNP masters can actively communicate with the B30 at one time.
The DNP Channels sub-menu is shown below.
PATH: SETTINGS
PRODUCT SETUP
 DNP CHANNELS
MESSAGE
The
and
DNP CHANNEL 1 PORT
for each channel. Once DNP is assigned to a serial port, DNP is the only protocol running on that port; Modbus or IEC
60870-5-103 are disabled. If DNP is assigned to RS485, the protocol must be set to DNP on the serial port configuration as
well, for the change to take effect. When the
DNP protocol can be used over TCP/IP on the Ethernet ports. When the
UDP," the channel 1 DNP protocol can be used over UDP/IP on the Ethernet ports. See the DNP appendix for information
on the DNP protocol.
Changes to these settings take effect when power has been cycled to the relay.
Do not set more than one protocol to the same TCP/UDP port number, as this results in unreliable operation of
NOTE
those protocols.
The
setting is the DNP slave address. This number identifies the B30 on a DNP communications link. Each
DNP ADDRESS
DNP slave should be assigned a unique address.
GE Multilin
DNP MESSAGE FRAGMENT
SIZE: 240
DNP OBJECT 1
DEFAULT VARIATION: 2
DNP OBJECT 2
DEFAULT VARIATION: 2
DNP OBJECT 20
DEFAULT VARIATION: 1
DNP OBJECT 21
DEFAULT VARIATION: 1
DNP OBJECT 22
DEFAULT VARIATION: 1
DNP OBJECT 23
DEFAULT VARIATION: 2
DNP OBJECT 30
DEFAULT VARIATION: 1
DNP OBJECT 32
DEFAULT VARIATION: 1
DNP NUMBER OF PAIRED
CONTROL POINTS: 0
DNP TCP CONNECTION
TIMEOUT: 120 s
setting is set to DNP 3.0. The B30 can be used as a DNP slave device con-
PROTOCOL


COMMUNICATIONS
DNP CHANNEL 1 PORT:
NETWORK
DNP CHANNEL 2 PORT:
COM2 - RS485
settings select the communications port assigned to the DNP protocol
DNP CHANNEL 2 PORT
DNP CHANNEL 1(2) PORT
B30 Bus Differential System
Range: 30 to 2048 in steps of 1
Range: 1, 2
Range: 1, 2, 3
Range: 1, 2, 5, 6
Range: 1, 2, 9, 10
Range: 1, 2, 5, 6
Range: 1, 2, 5, 6
Range: 1, 2, 3, 4, 5
Range: 1, 2, 3, 4, 5, 7
Range: 0 to 32 in steps of 1
Range: 10 to 7200 s in steps of 1
DNP PROTOCOL
DNP CHANNELS
Range: NONE, COM2 - RS485,
FRONT PANEL - RS232, NETWORK - TCP,
NETWORK - UDP
Range: NONE, COM2 - RS485,
FRONT PANEL - RS232, NETWORK - TCP
setting is set to "Network - TCP," the channel 1(2)
DNP CHANNEL 1 PORT
5.2 PRODUCT SETUP
SETTINGS
PRODUCT
setting is set to "Network -
5-37
5