B.4 MEMORY MAPPING
Table B–10: MODBUS MEMORY MAP (Sheet 30 of 64)
ADDR
REGISTER NAME
Phase Time Overcurrent (Read/Write Grouped
5900
Phase Time Overcurrent 1 Function
5901
Phase Time Overcurrent 1 Signal Source
5902
Phase Time Overcurrent 1 Input
B
5903
Phase Time Overcurrent 1 Pickup
5904
Phase Time Overcurrent 1 Curve
5905
Phase Time Overcurrent 1 Multiplier
5906
Phase Time Overcurrent 1 Reset
5907
Phase Time Overcurrent 1 Voltage Restraint
5908
Phase TOC 1 Block For Each Phase (3 items)
590F
Phase Time Overcurrent 1 Target
5910
Phase Time Overcurrent 1 Events
5911
Reserved (3 items)
5914
...Repeated for Phase Time Overcurrent 2
5928
...Repeated for Phase Time Overcurrent 3
593C
...Repeated for Phase Time Overcurrent 4
5950
...Repeated for Phase Time Overcurrent 5
5964
...Repeated for Phase Time Overcurrent 6
Phase Instantaneous Overcurrent (Read/Write Grouped Setting) (6 modules)
5A00
Phase Instantaneous Overcurrent 1 Function
5A01
Phase Instantaneous Overcurrent 1 Signal Source 0 to 5
5A02
Phase Instantaneous Overcurrent 1 Pickup
5A03
Phase Instantaneous Overcurrent 1 Delay
5A04
Phase Instantaneous Overcurrent 1 Reset Delay
5A05
Phase IOC1 Block For Each Phase (3 items)
5A0B
Phase Instantaneous Overcurrent 1 Target
5A0C
Phase Instantaneous Overcurrent 1 Events
5A0D
Reserved (6 items)
5A13
...Repeated for Phase Instantaneous Overcurrent
2
5A26
...Repeated for Phase Instantaneous Overcurrent
3
5A39
...Repeated for Phase Instantaneous Overcurrent
4
5A4C
...Repeated for Phase Instantaneous Overcurrent
5
5A5F
...Repeated for Phase Instantaneous Overcurrent
6
Neutral Time Overcurrent (Read/Write Grouped Setting) (6 modules)
5B00
Neutral Time Overcurrent 1 Function
5B01
Neutral Time Overcurrent 1 Signal Source
5B02
Neutral Time Overcurrent 1 Input
5B03
Neutral Time Overcurrent 1 Pickup
5B04
Neutral Time Overcurrent 1 Curve
5B05
Neutral Time Overcurrent 1 Multiplier
5B06
Neutral Time Overcurrent 1 Reset
5B07
Neutral Time Overcurrent 1 Block
B-38
RANGE
Setting)
(6 modules)
0 to 1
0 to 5
0 to 1
0 to 30
0 to 16
0 to 600
0 to 1
0 to 1
0 to 4294967295
0 to 2
0 to 1
0 to 1
0 to 1
0 to 30
0 to 600
0 to 600
0 to 4294967295
0 to 2
0 to 1
0 to 1
0 to 1
0 to 5
0 to 1
0 to 30
0 to 16
0 to 600
0 to 1
0 to 4294967295
B30 Bus Differential System
APPENDIX B
UNITS
STEP
FORMAT
---
1
F102
---
1
F167
---
1
F122
pu
0.001
F001
---
1
F103
---
0.01
F001
---
1
F104
---
1
F102
---
1
F300
---
1
F109
---
1
F102
---
1
F001
---
1
F102
---
1
F167
pu
0.001
F001
s
0.01
F001
s
0.01
F001
---
1
F300
---
1
F109
---
1
F102
---
1
F001
---
1
F102
---
1
F167
---
1
F122
pu
0.001
F001
---
1
F103
---
0.01
F001
---
1
F104
---
1
F300
DEFAULT
0 (Disabled)
0 (SRC 1)
0 (Phasor)
1000
0 (IEEE Mod
Inv)
100
0
(Instantaneou
s)
0 (Disabled)
0
0 (Self-reset)
0 (Disabled)
0
0 (Disabled)
0 (SRC 1)
1000
0
0
0
0 (Self-reset)
0 (Disabled)
0
0 (Disabled)
0 (SRC 1)
0 (Phasor)
1000
0 (IEEE Mod
Inv)
100
0
(Instantaneou
s)
0