B.4 MEMORY MAPPING
Table B–10: MODBUS MEMORY MAP (Sheet 10 of 64)
ADDR
REGISTER NAME
1D84
Frequency for Source 3
1D86
Frequency for Source 4
1D88
Frequency for Source 5
1D8A
Frequency for Source 6
B
Breaker Flashover (Read/Write Setting) (2 modules)
2196
Breaker Flashover 1 Function
2197
Breaker Flashover 1 Side 1 Source
2198
Breaker Flashover 1 Side 2 Source
2199
Breaker Flashover 1 Status Closed A
219B
Breaker Flashover 1 Status Closed B
219D
Breaker Flashover 1 Status Closed C
219F
Breaker Flashover 1 Voltage Pickup Level
21A0
Breaker Flashover 1 Voltage Difference Pickup
Level
21A2
Breaker Flashover 1 Current Pickup Level
21A3
Breaker Flashover 1 Pickup Delay
21A4
Breaker Flashover 1 Supervision Phase A
21A6
Breaker Flashover 1 Supervision Phase B
21A8
Breaker Flashover 1 Supervision Phase C
21AA
Breaker Flashover 1 Block
21AC
Breaker Flashover 1 Events
21AD
Breaker Flashover 1 Target
21AE
Reserved (4 items)
21B2
...Repeated for Breaker Flashover 2
Passwords Unauthorized Access (Read/Write Command)
2230
Reset Unauthorized Access
Field Unit Raw Data Settings (Read/Write Setting)
2460
Field Raw Data Port
2461
Field Raw Data Freeze
Bus Actuals (Read Only) (2 modules)
2500
Bus Differential IA Magnitude
2502
Bus Differential IA Angle
2503
Bus Differential IB Magnitude
2505
Bus Differential IB Angle
2506
Bus Differential IC Magnitude
2508
Bus Differential IC Angle
2509
Bus Differential Rest IA Magnitude
250B
Bus Differential Rest IA Angle
250C
Bus Differential Rest IB Magnitude
250E
Bus Differential Rest IB Angle
250F
Bus Differential Rest IC Magnitude
2511
Bus Differential Rest IC Angle
2515
Bus Maximum CT Primary
2517
Reserved (9 items)
2520
...Repeated for module number 2
Remote Double-Point Status Inputs (Read/Write Setting Registers) (5 modules)
2540
Remote Double-point Status Input 1 Device
2541
Remote Double-point Status Input 1 Item
2542
Remote Double-point Status Input 1 Name
B-18
RANGE
2 to 90
2 to 90
2 to 90
2 to 90
0 to 1
0 to 5
0 to 6
0 to 4294967295
0 to 4294967295
0 to 4294967295
0 to 1.5
0 to 100000
0 to 1.5
0 to 65.535
0 to 4294967295
0 to 4294967295
0 to 4294967295
0 to 4294967295
0 to 1
0 to 2
---
0 to 1
0 to 7
0 to 1
0 to 999999.999
-359.9 to 0
0 to 999999.999
-359.9 to 0
0 to 999999.999
-359.9 to 0
0 to 999999.999
-359.9 to 0
0 to 999999.999
-359.9 to 0
0 to 999999.999
-359.9 to 0
0 to 50000
---
1 to 32
0 to 64
1 to 64
B30 Bus Differential System
APPENDIX B
UNITS
STEP
FORMAT
Hz
0.001
F003
Hz
0.001
F003
Hz
0.001
F003
Hz
0.001
F003
---
1
F102
---
1
F167
---
1
F211
---
1
F300
---
1
F300
---
1
F300
pu
0.001
F001
V
1
F060
pu
0.001
F001
s
0.001
F001
---
1
F300
---
1
F300
---
1
F300
---
1
F300
---
1
F102
---
1
F109
---
---
F001
---
1
F126
---
1
F244
---
1
F102
A
0.001
F060
degrees
0.1
F002
A
0.001
F060
degrees
0.1
F002
A
0.001
F060
degrees
0.1
F002
A
0.001
F060
degrees
0.1
F002
A
0.001
F060
degrees
0.1
F002
A
0.001
F060
degrees
0.1
F002
---
1
F060
---
---
F001
---
1
F001
---
1
F606
---
1
F205
DEFAULT
0
0
0
0
0 (Disabled)
0 (SRC 1)
0 (None)
0
0
0
850
1000
600
100
0
0
0
0
0 (Disabled)
0 (Self-Reset)
0
0 (No)
6 (H1a)
0 (Disabled)
0
0
0
0
0
0
0
0
0
0
0
0
1
0
1
0 (None)
"RemDPS Ip
1"