5 SETTINGS
The
UNAUTHORIZED ACCESS
command. Therefore, to apply this feature with security, the command level should be password-protected. The
ALARMS
operand does not generate events or targets.
If events or targets are required, the
with event logs or targets enabled.
The access level timeout settings are shown below.
PATH: SETTINGS
PRODUCT SETUP
 ACCESS LEVEL
 TIMEOUTS
MESSAGE
These settings allow the user to specify the length of inactivity required before returning to the restricted access level. Note
that the access level will set as restricted if control power is cycled.
COMMAND LEVEL ACCESS TIMEOUT: This setting specifies the length of inactivity (no local or remote access)
required to return to restricted access from the command password level.
SETTING LEVEL ACCESS TIMEOUT: This setting specifies the length of inactivity (no local or remote access)
required to return to restricted access from the command password level.
DUAL PERMISSION SECURITY ACCESS
PATH: SETTINGS
PRODUCT SETUP
 DUAL PERMISSION
 SECURITY ACCESS
MESSAGE
MESSAGE
The dual permission security access feature provides a mechanism for customers to prevent unauthorized or unintended
upload of settings to a relay through the local or remote interfaces interface.
The following settings are available through the local (front panel) interface only.
LOCAL SETTING AUTH: This setting is used for local (front panel or RS232 interface) setting access supervision.
Valid values for the FlexLogic operands are either "On" (default) or any physical "Contact Input ~~ On" value.
If this setting is "On", then local setting access functions as normal; that is, a local setting password is required. If this
setting is any contact input on FlexLogic operand, then the operand must be asserted (set as on) prior to providing the
local setting password to gain setting access.
If setting access is not authorized for local operation (front panel or RS232 interface) and the user attempts to obtain
setting access, then the
UNAUTHORIZED ACCESS
If this setting is "Off," firmware upgrades are blocked. If this setting is "On," firmware upgrades are allowed.
REMOTE SETTING AUTH: This setting is used for remote (Ethernet or RS485 interfaces) setting access supervision.
If this setting is "On" (the default setting), then remote setting access functions as normal; that is, a remote password is
required). If this setting is "Off", then remote setting access is blocked even if the correct remote setting password is
provided. If this setting is any other FlexLogic operand, then the operand must be asserted (set as on) prior to provid-
ing the remote setting password to gain setting access.
If this setting is "Off," firmware upgrades are blocked. If this setting is "On," firmware upgrades are allowed.
ACCESS AUTH TIMEOUT: This setting represents the timeout delay for local setting access. This setting is applicable
when the
LOCAL SETTING AUTH
is continuously monitored for an off-to-on transition. When this occurs, local access is permitted and the timer pro-
grammed with the
ACCESS AUTH TIMEOUT
GE Multilin
operand is reset with the
COMMANDS
UNAUTHORIZED ACCESS

SECURITY
ACCESS SUPERVISION
COMMAND LEVEL ACCESS
TIMEOUT: 5 min
SETTING LEVEL ACCESS
TIMEOUT: 30 min

SECURITY
DUAL PERMISSION SECURITY ACCESS
LOCAL SETTING AUTH:
On
REMOTE SETTING AUTH:
On
ACCESS AUTH
TIMEOUT: 30 min.
message is displayed on the front panel.
setting is programmed to any operand except "On". The state of the FlexLogic operand
setting value is started. When this timer expires, local setting access is
B30 Bus Differential System

CLEAR RECORDS
operand can be assigned to a digital element programmed
ACCESS LEVEL TIMEOUTS
Range: 5 to 480 minutes in steps of 1
Range: 5 to 480 minutes in steps of 1
Range: selected FlexLogic operands (see below)
Range: FlexLogic operand
Range: 5 to 480 minutes in steps of 1
5.2 PRODUCT SETUP

RESET UNAUTHORIZED
5-11
5

Advertisement

Table of Contents
loading