GE B30 Instruction Manual page 194

Ur series bus differential system protection relay
Hide thumbs Also See for B30:
Table of Contents

Advertisement

5.2 PRODUCT SETUP
 POINT 0
 POINT 95
The binary input points are mapped using elements from a list of possible FlexLogic operands. A maximum of 96 binary
inputs (points) can be mapped this way.
The IEC60870-5-103 point list always starts with point 0 and ends at the first "Off" value. Since the IEC 60870-5-103 point
list must be in a continuous block, any points assigned after the first "Off" point are ignored.
5
For each defined point, set appropriate values for the Function Type (FUN) and Information Number (INF), which form the
Information Object Identifier field of the ASDU, as defined in IEC60870-5-103.
The binary input points are sent as Class 1 data. They are sent either as a response to a general interrogation received
from the controller or reported spontaneously. Spontaneous transmission occurs as a response to cyclic Class 2 requests.
If the B30 wants to transmit Class 1 data at that time, it demands access for Class 1 data transmission (ACD=1 in the con-
trol field of the response).
For any change to take effect, restart the relay.
PATH: SETTINGS
PRODUCT SETUP
 IEC103 INPUTS
 MEASURANDS
5-60
POINT 0 FUN
0
POINT 0 INF
MESSAGE
0
POINT 0 Input
MESSAGE
Off
POINT 95 FUN
0
POINT 95 INF
MESSAGE
0
POINT 95 Input
MESSAGE
Off

COMMUNICATIONS
 ASDU 1
 ASDU 2
MESSAGE
 ASDU 3
MESSAGE
 ASDU 4
MESSAGE
B30 Bus Differential System
Range: 0 to 255 in steps of 1
Range: 0 to 255 in steps of 1
Range: FlexLogic operand
Range: 0 to 255 in steps of 1
Range: 0 to 255 in steps of 1
Range: FlexLogic operand

IEC60870-5-103
IEC103 INPUTS MEASURANDS
Range: see sub-menu below
Range: see sub-menu below
Range: see sub-menu below
Range: see sub-menu below
5 SETTINGS
GE Multilin

Advertisement

Table of Contents
loading

Table of Contents