Power Control; A.10 Power Control - Siemens SITRANS F Operating Instructions Manual

Communication modules sitrans f m mag 8000 modbus rtu
Hide thumbs Also See for SITRANS F:
Table of Contents

Advertisement

Modbus holding registers

A.10 Power control

Modbus
Data type /
register
Size [bytes]
4:3017
uint16 / 2
4:0050
date / 6
A.10

Power control

Table A- 11
Power control
Modbus
Data type /
register
Size [bytes]
4:0368
uint8 / 1
4:3030
uint8 / 1
56
Parameter
Description
Fault status
2 bytes describing which er-
rors/warnings are active
Date of fault log reset
Date of fault log reset
Parameter
Description
Mains frequency
Country related mains power
frequency for enabling correct
noise filtering
Power supply
Meter power supply source
Bit 1: Insulation error
Bit 2: Coil current error
Bit 3: Preamplifier overload
Bit 4: Database checksum
error
Bit 5: Low power warning
Bit 6: Flow overload warning
Bit 7: Pulse A overload warning
Bit 8: Pulse B overload warning
Bit 9: Consumption interval
warning
Bit 10/L: Leakage warning
Bit 11/E: Empty pipe warning
Bit 12/C: Low impedance
warning
Bit 13/d: Flow limit warning
Bit 14/A: Reverse flow warning
Bit 15: Not used
Bit 16: Not used
0 = 50 Hz
1 = 60 Hz
0 = Battery
1 = Mains supply
Operating Instructions, 04/2016, A5E03409989-AB
Default value
Access level
[unit] /
Value range
- [-]
Read Only
- [-]
Read Only
Default value
Access level
[unit] /
Value range
-
[-]
Read Only
1)
- [-]
Read Only
MAG 8000 Modbus RTU