Connecting
Note
Shielding
Always shield a Modbus over Serial Line Cable. At one end of each cable its shield must be
connected to protective ground. If a connector is used at this end, the shell of the connector
is connected to the shield of the cable.
Note
Cable specifications
A RS 485-Modbus must use a balanced pair (for D0-D1) and a third wire (for the Common).
For the balanced pairs used in an RS 485-system, a Characteristic Impedance with a value
between 100 and 120 Ohms must be used.
4.1
Wiring
● Connect shield to MAG 8000 enclosure using the cable clamp
Image 4-1
MAG 8000 Modbus RTU
Operating Instructions, 04/2016, A5E03409989-AB
Cable shield connection