Modbus Application Settings - Siemens SITRANS F Operating Instructions Manual

Communication modules sitrans f m mag 8000 modbus rtu
Hide thumbs Also See for SITRANS F:
Table of Contents

Advertisement

Modbus holding registers
A.2 MODBUS application settings
A.2

MODBUS application settings

Table A- 1
Customer profile
Modbus
Data type /
register
Size [bytes]
4:2009
string / 6
4:0010
string / 6
4:0657
string / 16
4:0665
string / 16
Table A- 2
Measurement
Modbus
Data type /
register
Size [bytes]
4:3001
float32 / 4
4:3003
float32 / 4
4:3005
float32 / 4
4:3007
float32 / 4
4:3048
date / 6
4:3009
sint32 / 4
4:3011
sint32 / 4
4:3013
float32 / 4
44
Parameter
Description
Meter access code
Password to change parameters
in the water meter
New access code
Downloaded password is pro-
tected and can not be read.
New password can be changed
when old password is entered or
if hardware key is mounted.
Application identifier
Customer application identification
information (max 15 characters)
Application location
Customer application location
information (max 15 characters)
Parameter
Description
Actual velocity
Actual velocity in mm/s
Flow rate
Actual flow value
Insulation value
Insulation value from last insula-
tion test
Insulation tests ful-
Number of insulation tests since
filled
last power up
Insulation test date
Date of last insulation test
Electrode impedance
Electrode impedance A for empty
A
pipe detection
Electrode impedance
Electrode impedance B for empty
B
pipe detection
Flowrate percent
Flowrate as percent of Qn
value
Default value
[unit] /
Value range
1000 [-]
1000 [-]
Identity [-]
Location [-]
Default value
[unit] /
Value range
- [mm/s]
- [-]
1)
- [mm/s]
- [-]
- [-]
- [ohm]
- [ohm]
- [%]
MAG 8000 Modbus RTU
Operating Instructions, 04/2016, A5E03409989-AB
Access level
Write
Write
Read / Write
Read / Write
Access level
Read Only
Read Only
Read Only
Read Only
Read Only
Read Only
Read Only
Read Only