Implementing Sleep Mode - GE MDS SD4A Technical Manual

Mds sd4 series
Table of Contents

Advertisement

How Sleep Mode
Works
Sleep Mode Example
94

8.4 Implementing Sleep Mode

Sleep Mode places the transceiver into a low power "hibernating" state,
with a nominal current draw of less than 10 mA (at 13 Vdc) and a
"wake-up" time of approximately 50 milliseconds. Sleep Mode is often
used at battery/solar-powered sites to conserve power.
The ability to enter Sleep Mode is controlled through the Device Set-
tings Screen (see "Device Settings" on Page 43), but an active low on
COM2
Pin 4 of the
port is what actually places the radio in Sleep Mode.
NOTE: Sleep mode is not intended for use on a master radio.
When Sleep Mode is enabled via the Device Settings Screen, the state
COM2
of Pin 4 on
is continuously monitored to detect a request to enter
sleep mode from an external device (RTU, PLC, etc.). For ease of use,
there are certain conditions which temporarily override the sleep request
to prevent unwanted behavior of the radio. These conditions are:
1. The radio must be powered up for at least 60 seconds before it is
allowed to enter sleep mode.
2. Any user-originated activity on the console terminal disables
entering sleep mode for 30 seconds, measured from the time of last
keystroke.
3. When locally reprogramming the transceiver's firmware, sleep
mode is disabled throughout the reprogramming time, and is sup-
pressed for 30 seconds thereafter.
4. The passage of payload data does not inhibit sleep mode.
This section describes how to implement Sleep Mode in a typical sce-
nario. Before using Sleep Mode, the following conditions must be met
to provide proper operation and avoid damage to the transceiver:
a. Sleep Mode must be enabled on the radio's Device Settings
Screen.
b. Output voltage to the radio must not exceed +5.0 Vdc.
c. Output voltage to wake up the radio must be between +2.0 Vdc
and +5.0 Vdc.
d. Output voltage to enter Sleep Mode must be +0.6 Vdc or less.
With the above conditions met, you are ready to use Sleep Mode. As a
working example, suppose you need communication to each Remote
site in your network only once per hour. Program the RTU/PLC at the
Remote sites to raise an RS-232 line once each hour (DTR for example),
SD Series Technical Manual
MDS 05-4846A01, Rev. F