Smoke Detector - Notifier NFS2-3030 Operation Manual

Fire alarm control panel
Hide thumbs Also See for NFS2-3030:
Table of Contents

Advertisement

Read Status
Special Function Zone
Trouble Zone
DAA Speaker CKT
* The Nxxx preface to all the above address formats refers to the node number, where N = node, xxx = the network node number.
Enter an address to view its attributes (the cursor will be in the underlined section).
NEXT POINT/PREVIOUS POINT - Press to view next or previous point.
ACCEPT - Press to accept the displayed point for further viewing.
Pressing the ACCEPT soft key on the Point Select Screen will display the information that corre-
sponds to the chosen point. Each point type has its own screen.
NOTE: The first four lines of the display may indicate an alarm for a point unrelated to the
requested point information displayed below them.

3.2 Smoke Detector

When a detector address is entered into the Point Select Screen and the ACCEPT soft key is
pressed, the following screen will display if the detector is a smoke detector.
For FSC-851 detectors, the values appear in line
14 above. Refer to More Information on page 19
for explanation of fields.
Display
Lines 1- 4 - This could display any current event message, or, as in this example, the System Nor-
mal message.
Line 5 - This line contains the screen title and the address of the point being read.
52
Type
Address Format*
NxxxZFxx
NxxxZTyyy
NxxxAyySn
Table 3.1 Address Formats (2 of 2)
L A K E V I E W G E N E R A L H O S P I T A L
1 0 : 2 2 : 3 4 A
T U E J A N 2 5 , 2 0 1 1
R E A D A D D R E S S : N 1 2 4 L 0 3 D 0 5 2
A U T O M A T I C
E L E V A T O R L O B B Y
F I F T H F L O O R
Z 0 0 5 ,
Z 0 2 7 ,
,
V A L U E S : 0 1 1 % O F A L A R M , 0 4 5 % O F P R E A L A R M
A L A R M : 6 = 1 . 6 6 % , P R E A L A R M : 3 = 0 . 4 7 %
A C T I O N / S T A T U S : N O N E / V E R Y C L E A N
P E A K S : 5 6 % V E R I F Y C O U N T : 0 2 C O - O P : D 1 0 0 , 1 5 8
1 0 : 2 2 : 3 4 A T U E J A N 2 5 , 2 0 1 1
P E A K S : 5 6 % C O U N T : 0 2 C O : 2 0 0 P P M T E M P : 1 0 0
Figure 3.2 Smoke Detector Screen - Read Status
ZF=Special Function Zone, x=Special Function Zone number
(00, 01 - 07, 09 - 22)
ZT=Trouble Zone, yyy=Trouble Zone number (1-100)
N indicates Node number, xxx=DVC/DVC-EM Node number, A
indicates DAA-5025 or DAA-5070 Audio Amplifier, yy=DAA
address (01 through 32), S indicates Speaker circuit, n =
Speaker circuit number (1-4).
S Y S T E M N O R M A L
I N A C T I V E
E A S T W I N G
Z 0 0 5
S M O K E ( P H O T O )
Z 0 6 6 ,
,
,
NFS2-3030 Operations Manual — P/N 52546:N1 06/20//2014
Smoke Detector
,
,
,
,
B A C K
o
F

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents