Notifier NFS2-3030 Operation Manual page 79

Fire alarm control panel
Hide thumbs Also See for NFS2-3030:
Table of Contents

Advertisement

Alphabetical List
Software Type ID Code
GEN ALARM
GEN PEND
GEN SUPERVIS
GEN TROUBLE
HAZARD ALERT
HEAT
HEAT+
HEAT(FIXED)
HEAT(ROR)
HEAT DETECT
HORN CIRCUIT
INST RELEASE
ISOLATED NAC
ISOLATED SPK
LATCH SUPERV
MAN RELEASE
MAN REL DELAY
MONITOR
MNS CONTROL
MNS GENERAL
MNS RELAY
MNS SPEAKER
MNS STROBE
NON FIRE
NONRESET CTL
PAS INHIBIT
P/CO (C SUP)
P/CO (P SUP)**
PHOTO/CO
POWER MONITR
PROCESS AUTO
PROCESS MON
PULL STATION
REL AUDIBLE
REL END BELL
REL CKT ULC
RELAY
NFS2-3030 Operations Manual — P/N 52546:N1 06/20//2014
Control module, XPC-8 circuit, or XP5-C (NAC mode) configured as a Municipal Box
Transmitter for NFPA 72 Auxiliary Fire Alarm Systems applications (MBT-1 required). This
Type ID can also be used for general alarm activation. It is programmed as "switch inhibit".
Control module, XPC-8 circuit, or XP5-C (NAC mode) that will activate upon receipt of an alarm
and/or trouble condition, and remain in the ON state until all events have been acknowledged
Control module, XPC-8, or XP5-C (NAC mode) activated under any supervisory condition
(includes sprinkler type). It is programmed as "switch inhibit"
Control module, XPC-8, or XP5-C (NAC mode) activated under any System Trouble condition.
It is programmed as "switch inhibit"
Indicated a hazard condition, tracking
Adjustable threshold heat detector
Adjustable threshold heat detector with a low temperature warning.
Intelligent 135ºF thermal sensor detector
15ºF per minute rate-of-rise detector
Monitor for conventional heat detector
Control module relay module used with NAC with horns
Control module used with NAC. Always non-silenceable and switch-inhibited
Supervised NAC for notification appliance, used with audio isolators. Activates even if there is
a short on its NAC circuit. Canada installations only.
Supervised NAC for speaker circuit, used with audio isolators. Activates even if there is a short
on its audio circuit. Canada installations only.
Indicates latching supervisory condition
Monitor module that provides manual release for a releasing zone through connection to a UL-
listed pull station
Monitor module that provides manual release with a 10 second delay for a releasing zone
through connection to a UL-listed pull station
Alarm-monitoring device
Activates control module mass notification devices when an MNS event occurs
Activates NAC mass notification devices when an MNS event occurs
Activates relay mass notification devices when an MNS event occurs
Activates speaker mass notification devices when an MNS event occurs
Activates strobe mass notification devices when an MNS event occurs
Monitors non fire activations
Output unaffected by "System Reset" command
Monitor used to inhibit Positive Alarm Sequence (PAS)
For use with a Photo/CO detector. If the CO element in the detector activates, a supervisory
condition is generated on the fire panel. An activation via the heat or photo element of the
Photo/CO detector will generate an alarm condition on the panel.
For use with a Photo/CO detector. If the photo element in the detector activates, a supervisory
condition is generated on the fire panel. An activation via the CO or heat element of the
Photo/CO detector will generate an alarm condition on the panel.
For use with a Photo/CO detector. Activation of the CO, photo or heat elements will generate
an alarm condition on the fire panel.
Monitor for main and auxiliary power supplies
Indicates process condition, tracking
Indicates process condition, latching
Manual fire-alarm activating device
Activates audio or visual devices steady when releasing starts
Control module used to activate NAC audio or visual device when releasing circuits shut off
Control module used to direct outputs to perform a release function as required by ULC
Form-C relay control module
Table A.1 Software Type ID Codes, Alphabetical List (2 of 4)
Software Type ID Codes
Device
79