Applications
b.
6.
Refer to the NFS2-3030 Programming Manual for instructions on setting the Soak Timer.
The FCM-1-REL module must be programmed with the correct releasing type code listed in the
NFS2-3030 Programming Manual.
4.9 Connecting an NBG-12LRA Agent Release-Abort Station
Typical Connections Figure 4.14 shows typical connections for wiring an NBG-12LRA Agent
Release-Abort Station.
NBG-12LRA
See Document 51369 for
installation details.
ELR mode R-47K
supervised and
power-limited
24 VDC power
from FACP's
main power supply
24 VDC UL-listed
releasing device
Brown
REL-47K
(use with Type Code
"Rel Ckt ULC")
Figure 4.14 Typical Connections for an NBG-12LRA Agent Release-Abort Station
NOTE: See Circuit Requirements for Section 4.7, "Connecting a Releasing Device to FCM-1
Control Modules (Retrofit applications only)", on page 53.
NOTE: Devices for use in releasing applications must be programmed as type code RELEASE
CIRCUIT or REL CKT ULC.
4.10 Connecting an FAAST Intelligent Aspiration Detector
The FAAST Intelligent Aspiration detector may be used to provide early warning fire protection
using aspiration sensing technology.
56
Circuits are supervised against opens and shorts.
Manual Abort
Manual Release
Normal
Release
System
Common (–)
Red
Connecting an NBG-12LRA Agent Release-Abort Station
FMM-101
Black
Yellow
Red
Violet
FMM-101
Yellow
Black
Red
Violet
Non-resettable +24 VDC from
AMPS-24/E
FRM-1
C.
N.C.
N.O.
FCM-1
NFS2-3030/E Installation Manual — P/N 52544:N1 07/18/2014
SLC loop to
FACP's
LCM-320 or
LEM-320
*If the SLC device does
not match the one in this
figure, refer to the SLC
manual appendix, which
contains wiring conversion
charts for type V and type
H modules.