Fire Alarm Control Panel
NFS2-3030/E

Installation Manual

Document 52544
N1
07/18/2014
Rev:
P/N 52544:N1
ECN 13-0838

Advertisement

Table of Contents
loading

Summary of Contents for Notifier NFS2-3030/E

  • Page 1: Installation Manual

    Fire Alarm Control Panel NFS2-3030/E Installation Manual Document 52544 07/18/2014 Rev: P/N 52544:N1 ECN 13-0838...
  • Page 2 Adequate written records of all inspections (especially in bedrooms), smoking in bed, and violent explosions should be kept. Limit-D-1-2013 NFS2-3030/E Installation Manual — P/N 52544:N1 07/18/2014...
  • Page 3: Installation Precautions

    HARSH™, NIS™, and NOTI•FIRE•NET™ are all trademarks; and Acclimate® Plus, FlashScan®, NION®, NOTIFIER®, ONYX®, ONYXWorks®, UniNet®, VeriFire®, and VIEW® are all registered trademarks of Honeywell International Inc. Echelon® is a registered trademark and LonWorks™ is a trademark of Echelon Corporation.
  • Page 4 •Brief description of content you think should be improved or corrected •Your suggestion for how to correct/improve documentation Send email messages to: FireSystems.TechPubs@honeywell.com Please note this email address is for documentation feedback only. If you have any technical issues, please contact Technical Services. NFS2-3030/E Installation Manual — P/N 52544:N1 07/18/2014...
  • Page 5: Table Of Contents

    3.14: Installing Printers............................38 3.14.1: Printer Installation Sequence ......................39 3.14.2: Configuring the Printer........................40 3.15: Wiring a Signaling Line Circuit (SLC)......................41 3.15.1: SLC Overview ..........................41 3.15.2: SLC Capacity...........................41 3.15.3: SLC Installation..........................42 3.16: Connecting a PC for Programming......................42 NFS2-3030/E Installation Manual — P/N 52544:N1 07/18/2014...
  • Page 6 A.3: Notification Appliance Circuits ........................62 A.4: Wire Requirements............................62 B.1: Standalone Application ..........................64 B.2: Local Network Application .........................64 B.3: Automatic Alarm Signal Silence.........................64 B.4: Annunciator Applications ...........................64 B.5: Releasing Devices ............................64 B.6: Canadian SLC Devices..........................64 NFS2-3030/E Installation Manual — P/N 52544:N1 07/18/2014...
  • Page 7: Section 1: About This Manual

    Underwriters Laboratories of Canada (ULC) • ULC-S527-99 Standard for Control Units for Fire Alarm Systems • ULC S524 Standard for the Installation of Fire Alarm Systems Other • EIA-485 and EIA-232 Serial Interface Standards NFS2-3030/E Installation Manual — P/N 52544:N1 07/18/2014...
  • Page 8: Ul 864 Compliance

    The following products have not received UL 864 9th Edition certification and may only be used in retrofit applications. Operation of the NFS2-3030/E with products not tested for UL 864 9th Edition has not been evaluated and may not comply with NFPA 72 and/or the latest edition of UL 864.
  • Page 9 XP6-C Supervised Control Module Installation Document I56-1805 XP6-MA Six Zone Interface Module Installation Document I56-1806 XP6-R Six Relay Control Module Installation Document I56-1804 FSA-8000 FAAST Intelligent Aspiration Sensing Technology Document I56-3903 Table 1.1 Related Documents (2 of 3) NFS2-3030/E Installation Manual — P/N 52544:N1 07/18/2014...
  • Page 10: Cautions And Warnings

    INFORMATION ABOUT PROCEDURES THAT COULD CAUSE PROGRAMMING ERRORS, RUNTIME ERRORS, OR EQUIPMENT DAMAGE. WARNING: SUMMARY IN BOLD INDICATES INFORMATION ABOUT PROCEDURES THAT COULD CAUSE IRREVERSIBLE DAMAGE TO THE CONTROL PANEL, IRREVERSIBLE LOSS OF PROGRAMMING DATA OR PERSONAL INJURY. NFS2-3030/E Installation Manual — P/N 52544:N1 07/18/2014...
  • Page 11: Section 2: System Overview

    Connections to easily mount from one to ten Signaling Line Circuit (SLC) loops • Network operation • Uses Notifier’s VIEW® early warning fire detection and the FlashScan® or CLIP families of detectors and modules • Alarm, Trouble, Supervisory and Security relays •...
  • Page 12: 2: Options

    THIS PRODUCT HAS BEEN CERTIFIED TO COMPLY WITH THE REQUIREMENTS IN THE STANDARD FOR CONTROL UNITS AND ACCESSORIES FOR FIRE ALARM SYSTEMS, UL 864 9TH EDITION. OPERATION OF THE NFS2-3030/E WITH PRODUCTS NOT TESTED FOR UL 864 9TH EDITION HAS NOT BEEN EVALUATED AND MAY NOT COMPLY WITH NFPA 72 AND/OR THE LATEST EDITION OF UL 864.
  • Page 13 Annunciators The NFS2-3030 supports ACM-24AT/ACM-48A (and their expanders) with either 64 or 96 points at an address, as well as ACM-16AT/ACM-32A/LDM-32 (and their expanders) with 64 points at an address and Notifier’s other ACS devices. (See Section 2.5 “Compatible Equipment” if looking for specific ACS devices.)
  • Page 14: Product Diagram

    Power Sources and Outputs”) Note: Dotted line indicates location of optional keypad & LCD display *Circuits marked with an asterisk are supervised by communication loss. See Appendix A, “Electrical Specifications” for details. Figure 2.1 CPU Connections NFS2-3030/E Installation Manual — P/N 52544:N1 07/18/2014...
  • Page 15: 1: Main Power Supply

    See Section 3.10, “Connecting Power Sources and Outputs”, on page 33 for basic wiring connections; see the AMPS-24/E Manual for complete details. Refer to the AMPS-24/E Manual to determine whether your system requires an auxiliary power supply. NFS2-3030/E Installation Manual — P/N 52544:N1 07/18/2014...
  • Page 16: System Cabinets

    TM-4 or NCM/HS-NCM. For information on audio chassis and dress panels, refer to the DVC Digital Voice Command Manual. NFS2-3030/E Installation Manual — P/N 52544:N1 07/18/2014...
  • Page 17: Compatible Equipment

    System Overview 2.5 Compatible Equipment Compatible Notifier and System Sensor equipment that connects directly to the CPU is listed below. These are the most common devices at time of publishing; the most complete list of compatible intelligent SLC loop devices is provided in the SLC Wiring Manual; for conventional non-addressable equipment see the Device Compatibility Document.
  • Page 18: System Sensor Compatible Equipment

    EOLR-1 End of Line Resistor Assembly FSB-200 Single-ended beam smoke detector. Retrofit Equipment: Compatible Notifier Equipment Listed Under Previous Editions of UL 864 NOTE: The products in this list have not received UL 864 9th Edition certification and may only be used in retrofit applications (see Section 1.2, “UL 864 Compliance”, on page 8).
  • Page 19: Section 3: Installation

    Amplifiers Manual, DVC-RPU Manual, AA-series Audio Amplifiers Manual, DS-DB Manual  Annunciators and other ACS devices Installation document for the specific device (such as ACS Manual, ACM-8R Manual, etc.) Table 3.1 Installation Checklist (1 of 2) NFS2-3030/E Installation Manual — P/N 52544:N1 07/18/2014...
  • Page 20: Mounting A Cabinet

    Use the four holes in the back surface of the backbox to provide secure mounting (See Figure 3.1). • Mount the backbox on a surface that is in a clean, dry, vibration-free area. NFS2-3030/E Installation Manual — P/N 52544:N1 07/18/2014...
  • Page 21 CAB-4 Series backbox, A-size (one-row) Keyholes 2 places Mounting holes 2 places Chassis- Chassis- mounting mounting studs studs (2 per row of (2 per row of backbox) backbox) Figure 3.1 Backbox-Mounting Holes and Chassis-Mounting Studs NFS2-3030/E Installation Manual — P/N 52544:N1 07/18/2014...
  • Page 22: Laying Out Equipment In Cabinet And Chassis

    Figure 3.6. See Section 3.5.2, “Mounting in the CA-2 Audio System Chassis” and Half-chassis for the CA-2 Installation Document. DVC and optional NCM/HS-NCM. Figure 3.3 CA-2 Audio Chassis Assembly NFS2-3030/E Installation Manual — P/N 52544:N1 07/18/2014...
  • Page 23: Attaching The Cpu & Chassis

    CPU2-3030D (with keypad/display) requires the longer stand-offs: 1.5 inch (38.1 mm); CPU2-3030ND (without keypad/display) requires the shorter stand-offs: 0.25 inch (6.35 mm) Slide circuit-board tabs into slots on chassis as shown in Figure 3.5. NFS2-3030/E Installation Manual — P/N 52544:N1 07/18/2014...
  • Page 24: 2: Mounting In The Ca-2 Audio System Chassis

    (DVC) • a microphone and telephone handset well • a microphone Figure 3.6 CA-2 Chassis Assembly CA-2 can also mount TELH-1, an optional telephone handset. NFS2-3030/E Installation Manual — P/N 52544:N1 07/18/2014...
  • Page 25: 3: Mounting Chassis In Backbox

    This battery’s shelf-life should exceed 10 years, but if for some reason it fails, the control panel will show a trouble when powered up. To replace the lithium battery: Make a full backup of all system settings to prevent loss of all programming data. Disconnect all power sources. NFS2-3030/E Installation Manual — P/N 52544:N1 07/18/2014...
  • Page 26: Attaching Option Boards

    CHS-M3 to the right of the CPU; additional modules can be mounted in other chassis. There are no slots in the first (back) two layers, but option boards with tabs (such as NCM-W) will still fit in those positions. NFS2-3030/E Installation Manual — P/N 52544:N1 07/18/2014...
  • Page 27: Mounting Procedures

    Control and Expander Modules”. NOTE: Mounting two pairs of loop-control and -expander modules in one chassis position may cause intermittent electrical interference. If this occurs, move one pair to a separate chassis position. NFS2-3030/E Installation Manual — P/N 52544:N1 07/18/2014...
  • Page 28: Connecting The Network Communications Module

    CHS-4L see Figure 3.14. NOTE: Mounting two pairs of loop control and expander modules in one chassis position may cause intermittent electrical interference. If this occurs, move one pair to a separate chassis position. NFS2-3030/E Installation Manual — P/N 52544:N1 07/18/2014...
  • Page 29: 2: Audio Applications With Chassis Ca-2

    LEM-320 mounted to it will be set to loop number 6. 3.8.4 Enabling External Power Supervision With LCM-320 revision 2.0 and higher, some type codes have external power supervision built into the software; see Section 4.2 “Devices Requiring External Power Supervision” for details. NFS2-3030/E Installation Manual — P/N 52544:N1 07/18/2014...
  • Page 30: 5: Installing A Multi-Layer Module Into The Chassis

    J2 LEM-320 Connection LCM-320 Connection SW1 Set to assign a unique SLC loop number LCM-320 LEM-320 Note: Do not cut any jumpers on the LCM-320 or LEM-320. Figure 3.11 LCM-320 and LEM-320 Diagram NFS2-3030/E Installation Manual — P/N 52544:N1 07/18/2014...
  • Page 31 NOTE: Depending on system components, clearance may be tight. Do not force modules! Move the assembly around gently until you find the angle where components and mounting studs pass each other without scraping together. NFS2-3030/E Installation Manual — P/N 52544:N1 07/18/2014...
  • Page 32 Figure 3.15 Connecting Multiple Pairs of Loop Control and Expander Modules Figure 3.15 Connecting Multiple Pairs of Loop Control and Expander Modules LCM-320 (in front) LEM-320 (in back) Figure 3.16 SLC Loop Connections on Loop-Control and Loop-Expander Modules NFS2-3030/E Installation Manual — P/N 52544:N1 07/18/2014...
  • Page 33: Form-C Relays On The Cpu

    Secondary power source. +24 VDC from batteries, installed in the control panel (or in an optional battery cabinet). Secondary (battery) power is required to support the system during loss of primary power. • External power sources. +24VDC auxiliary power supplies that are UL/ULC-listed for fire protective service. NFS2-3030/E Installation Manual — P/N 52544:N1 07/18/2014...
  • Page 34: 2: Connecting The Power Supply

    3.10.3 Checking AC Power Table 3.2 contains a checklist for checking the system with AC power applied to the main power supply: CAUTION: WHILE CHECKING AC POWER, MAKE SURE BATTERIES ARE NOT CONNECTED. NFS2-3030/E Installation Manual — P/N 52544:N1 07/18/2014...
  • Page 35: 4: Auxiliary Power Supply Connections

    NOTE: If additional knockouts are added to the backbox, proper separation of power-limited and non-power-limited Separating non-power-limited and wiring should be maintained. power limited circuits within the backbox with adhesive squares Figure 3.19 Typical Wiring in a Four-Row Backbox NFS2-3030/E Installation Manual — P/N 52544:N1 07/18/2014...
  • Page 36 NOTE: Relays are power-limited only when connected to power-limited sources for the relay outputs. NFS2-3030/E Installation Manual — P/N 52544:N1 07/18/2014...
  • Page 37: Central Station Fire Alarm System Canadian Requirements

    A HI B HI LED6 LED7 RCDA RCDB LED4 LED2 STATA STATB LED3 LED5 RECON PULSE1 LED1 LED8 RESET POWER TERM NCM-W NCA-2 Figure 3.20 Central Station Canadian Requirements for Second Dial-Out Connection NFS2-3030/E Installation Manual — P/N 52544:N1 07/18/2014...
  • Page 38: Ulc Remote Connection Feature

    The control panel can be configured to time-stamp the printout with the current time-of-day and date for each event. The printer can be located up to 50 feet (15.25 m) from the control panel. Installation and configuration instructions follow. NFS2-3030/E Installation Manual — P/N 52544:N1 07/18/2014...
  • Page 39: 1: Printer Installation Sequence

    Configure the printer as described in Section 3.14.2 “Configuring the Printer”. NOTE: Depending on which version of the AMPS-24/E is being used, the terminal block designations may differ from those listed. Please refer to the AMPS-24/E manual. NFS2-3030/E Installation Manual — P/N 52544:N1 07/18/2014...
  • Page 40: 2: Configuring The Printer

    Programming Manual for instructions.) • Data bits: 8 • Parity: None • Stop bits: 1 Table 3.4 Keltron DIP Switch Settings Set the printer DIP switches SP1 and SP2 according to settings in Table 3.4. NFS2-3030/E Installation Manual — P/N 52544:N1 07/18/2014...
  • Page 41: Wiring A Signaling Line Circuit (Slc)

    Loops must be programmed for Rapid Poll (refer to the programming manual for specific instructions). Modules on a fully loaded loop must adhere to a ratio of two monitor modules to one control module. NFS2-3030/E Installation Manual — P/N 52544:N1 07/18/2014...
  • Page 42: 3: Slc Installation

    NOTE: Download operations that change the basic program of the control panel must be performed by responsible service personnel in attendance at the control panel. After downloading a program, test the control panel in accordance with NFPA 72. NFS2-3030/E Installation Manual — P/N 52544:N1 07/18/2014...
  • Page 43: Section 4: Applications

    (Not required for contains wiring conversion FlashScan type codes charts for type V and type H modules. that provide built-in power supervision.) Figure 4.1 Enabling External Power Supervision Using Relays NFS2-3030/E Installation Manual — P/N 52544:N1 07/18/2014...
  • Page 44: Nfpa 72 Central Or Remote Station Fire Alarm System (Protected Premises Unit)

    NOTE: The following models do not comply with requirements for AC loss delay reporting when used with Central Station Protected Premises systems: AA-30, AA-120, AA-100, APS-6R, CHG-120. NOTE: For additional setup information for UDACT, refer to the UDACT Installation Manual. NFS2-3030/E Installation Manual — P/N 52544:N1 07/18/2014...
  • Page 45: Nfpa 72 Proprietary Fire Alarm Systems

    Uninterruptable Power Supply (UPS) 50 watt minimum, UL-listed for Fire Protective Signaling is recommended. A UPS is required for NFPA 72 Proprietary Protected Premises Receiving Unit Applications. Figure 4.3 Typical Proprietary Fire Alarm Systems Wiring Connections: Block View NFS2-3030/E Installation Manual — P/N 52544:N1 07/18/2014...
  • Page 46: Fire/Security Applications

    Security Module I/O Circuit Shielding - terminate the shield at earth ground at the junction box containing the module. • When employed as a Protected Premises Unit, the NFS2-3030 cabinet door must be wired with an STS-1 Tamper Switch that is monitored by the control panel. NFS2-3030/E Installation Manual — P/N 52544:N1 07/18/2014...
  • Page 47: 3: Installing A Security Tamper Switch

    Connect the STS-1 connector to J6 Security on the CPU. Program panel supervision for Tamper Input “Yes”. Connect to J6 Security STS-1 mounting location (side opposite of door hinges) Figure 4.5 Installing the STS-1 Security Tamper Switch NFS2-3030/E Installation Manual — P/N 52544:N1 07/18/2014...
  • Page 48: 4: Receiving Unit

    SLC manual appendix, which contains wiring conversion charts for type V and type H modules. UL-listed, normally-closed FMM-1 security switch Figure 4.6 Wiring Diagram for Proprietary Security Alarm Applications NFS2-3030/E Installation Manual — P/N 52544:N1 07/18/2014...
  • Page 49: 7: Connecting An Rks-S Remote Key Switch

    SLC manual appendix, which contains wiring conversion RKS-S rear charts for type V and type H modules. R-47K End-of-Line Resistor Figure 4.8 Connecting the FMM-1 Module to the RKS-S NFS2-3030/E Installation Manual — P/N 52544:N1 07/18/2014...
  • Page 50: 8: Single Tenant Security System With Entry/Exit Delay

    Programming Notes for Figure 4.9 Programming of Key Switch, Access Points, and Motion Detection RKS Remote Key Switch with Monitor Module Address: LXXMYYY (arbitrary) Type ID: ACCESS MONITOR Zone Map: (none) Custom Label: Arming Switch NFS2-3030/E Installation Manual — P/N 52544:N1 07/18/2014...
  • Page 51 Type ID: RELAY Zone Map: Custom Label: Security Group Output Signal Silence: No Walk Test: Yes/No (Installer Specified) Switch Inhibit: Yes B. MM Programming Address: LXXMYYY (arbitrary) Type ID: SECURITY-L Zone Map: (none) NFS2-3030/E Installation Manual — P/N 52544:N1 07/18/2014...
  • Page 52: 9: Security Annunciation

    Power-limited wiring • Supervised for open circuit only • Supervised for open circuit and shorts • Supervised for power loss • Supervised for power loss For more information, refer to the NFS2-3030 Programming Manual. NFS2-3030/E Installation Manual — P/N 52544:N1 07/18/2014...
  • Page 53: 3: Wiring

    End-of-Line device as shown in Figure 4.11. b) All wiring for releasing circuits is supervised against open and shorts. c) Program the releasing circuit for Type Code REL CKT ULC For applications not requiring power-limited circuits: NFS2-3030/E Installation Manual — P/N 52544:N1 07/18/2014...
  • Page 54 See figure 4.12. Refer to the SLC Manual for detailed wiring information. Monitor Module Mechanical Disconnect Switch listed for the application Note: Disconnect switch must provide separate dry contacts to indicate supervisory. Figure 4.12 Typical Connection of a Mechanical Disconnect Switch NFS2-3030/E Installation Manual — P/N 52544:N1 07/18/2014...
  • Page 55: Connecting Releasing Devices To Fcm-1-Rel Control Modules

    Do not loop wiring under the screw terminals. Break the wire run to provide supervision of connections. All applications using the FCM-1-REL are power-limited: Program the releasing circuit for Type Code REL CKT ULC or RELEASE CKT. NFS2-3030/E Installation Manual — P/N 52544:N1 07/18/2014...
  • Page 56: Connecting An Nbg-12Lra Agent Release-Abort Station

    NOTE: Devices for use in releasing applications must be programmed as type code RELEASE CIRCUIT or REL CKT ULC. 4.10 Connecting an FAAST Intelligent Aspiration Detector The FAAST Intelligent Aspiration detector may be used to provide early warning fire protection using aspiration sensing technology. NFS2-3030/E Installation Manual — P/N 52544:N1 07/18/2014...
  • Page 57 From Power Supply or Previous Device - For additional installation information for the FAAST detector, refer the FSA-8000 FAAST Installation and Maintenance Instruction document (I56-3903) and the SLC Wiring Manual Figure 4.15 FSA-8000A Connection to the FACP (51253). NFS2-3030/E Installation Manual — P/N 52544:N1 07/18/2014...
  • Page 58: Section 5: Testing The System

    The minimum DC resistance between conductors of an unpopulated SLC pair cannot be less than 1 K ohms. Measure DC resistance on an unpopulated loop as shown in Figure 5.1 on page 59. continued… NFS2-3030/E Installation Manual — P/N 52544:N1 07/18/2014...
  • Page 59: Battery Checks And Maintenance

    If Sulfuric Acid gets into eyes, seek immediate medical attention. • Ensure proper handling of the battery to prevent short circuits. • Take care to avoid accidental shorting of the leads from uninsulated work benches, tools, bracelets, rings, and coins. NFS2-3030/E Installation Manual — P/N 52544:N1 07/18/2014...
  • Page 60 Testing the System Battery Checks and Maintenance CAUTION: SHORTING THE BATTERY LEADS CAN DAMAGE THE BATTERY, EQUIPMENT, AND COULD CAUSE INJURY TO PERSONNEL. NFS2-3030/E Installation Manual — P/N 52544:N1 07/18/2014...
  • Page 61 Notes NFS2-3030/E Installation Manual — P/N 52544:N1 07/18/2014...
  • Page 62: A.1: Operating Power

    NOTE: If running an SLC in conduit with Notification Appliance Circuits, you can reduce problems by exclusively using electronic sounders (such as the MA/SS-24 Series) instead of more electronically noisy notification appliances (such as electromechanical bells or horns). NFS2-3030/E Installation Manual — P/N 52544:N1 07/18/2014...
  • Page 63 +24 VDC power to devices within the same enclosure as the CPU. If those devices have outputs, the outputs must be power-limited. Power rating is determined by the power source(s). See Section 3.10.1 “Overview”, and the AMPS-24 Manual for more details. NFS2-3030/E Installation Manual — P/N 52544:N1 07/18/2014...
  • Page 64: B.1: Standalone Application

    Supervision for shorts is required; use REL-47K and type code Rel Ckt ULC. Refer to Section 4.6 “Releasing Applications”. B.6 Canadian SLC Devices For a complete list of ULC-listed SLC loop devices, see SLC Wiring Manual, Appendix C “Canadian Versions of SLC Devices”. NFS2-3030/E Installation Manual — P/N 52544:N1 07/18/2014...
  • Page 65 Electrical Connections 33 tem 44 Electrical Specifications 62 NFPA 72 Remote Station Fire Alarm Sys- Enclosures, see Backboxes 16 tem 44 External Power Supervision 43 Overview 43 Protected Premises Unit 44 Non-Power-Limited Circuits NFS2-3030/E Installation Manual — P/N 52544:N1 07/18/2014...
  • Page 66 Service 58 Signalling Line Circuit, also see SLC 41 SLC Loop Modules External Power Supervision 43 SLC Loop Number 29 SLC, also see SLC Wiring Manual Specifications 62 SLC, see SLC Wiring Manual NFS2-3030/E Installation Manual — P/N 52544:N1 07/18/2014...
  • Page 67 Manufacturer's Return Material Authorization form. The replacement part shall come from Manufacturer's stock and may be new or refurbished. THE FOREGOING IS DISTRIBUTOR'S SOLE AND EXCLUSIVE REMEDY IN THE EVENT OF A WARRANTY CLAIM. Warn-HL-08-2009.fm NFS2-3030/E Installation Manual — P/N 52544:N1 07/18/2014...
  • Page 68 World Headquarters 12 Clintonville Road Northford, CT 06472-1610 USA 203-484-7161 fax 203-484-7118 www.notifier.com...