Printing Reports
DETECT MAINTENANCE REPORT: Press this soft key to print a list from the printer connected
to the control panel that contains the detector maintenance status for each installed addressable
detector. The report looks like this:
******DETECTOR MAINTENANCE******************************************************
NORMAL SMOKE(LASER) Detector
Alarm:
NORMAL SMOKE ACCLIM Detector
Alarm:
Field Identification
Detector Maintenance Report
State
NORMAL SMOKE(LASER) Detector
Alarm:
Percent of
alarm
threshold*
* Whichever occupancy value is in effect when the report is printed.
INSTALLED POINTS: Press this soft key to display the Installed Points Menu screen.
70
000% PreAlarm:
000% A6P6 V000
000% PreAlarm:
000% A8P8 V000
Current reading of raw analog
value in microseconds
Label
000% PreAlarm:
000% A6P6 V000
Percent of
prealarm
threshold*
L01D001 000330us 000340us
L01D002 000030us 000000us
Long term average of
raw analog value in
microseconds
Extended
Label
L01D001 000330us 000340us
Verification count
Programmed prealarm sensitivity*
Programmed alarm sensitivity*
NFS2-3030 Operations Manual — P/N 52546:N1 06/20//2014
Printer Functions Screen
Comp:000% Pk: 002%
L01D001
Comp:000% Pk: 000%
L01D002
Compensation
percentage
Detector peak
Comp:000% Pk: 002%
L01D001
Address