Operation of the Control Panel
TROUBLE MESSAGE TYPE
LOADING...NO SERVICE
LOCAL MIC TROUBLE
LOCAL PHONE TROUBLE
LOOP x- x COMM FAILURE
MAN EVAC INITIATED
MAN EVAC RECEIVED
MANUAL MODE ENTERED
MODBUS COMMUNICATIONS FAULT The VESDA Gateway can not communicate with the HLI, the HLI may be damaged or not powered, or the
NCM COMM LOSS
NCM CONNECTION LIMIT EXCEEDED
NCM SNIFFER MODE ACTIVE
NETWORK FAIL PORT x
NETWORK INCOMPATIBILITY
NETWORK MAPPING LIMIT
EXCEEDED
NFN PAGING CHANNEL LIMIT
EXCEEDED
NFPA 24HR REMINDER
NVRAM BATT TROUBLE
NO DEV. INST ON L1
NO POWER SUPPLY INST
PANEL DOOR OPEN
PHONE CHANNEL LIMIT EXCEEDED
POWER SUPPLY TROUBLE
PRIMARY AMP x FAIL
PRIMARY AMP x HARDWARE FAIL
PRIMARY AMP x LIMIT
PRIMARY AMP x OVERCURRENT
PRIMARY AMP x TRIP
PRINTER OFF LINE
PRINTER PAPER OUT
PROGRAM CORRUPTED
PROG MODE ACTIVATED
REMOTE DISPLAY x NO ANSWER
REMOTE DISPLAY x TROUBLE
REMOTE MIC TROUBLE
SELF TEST FAILED
SOFTWARE MISMATCH
STYLE 4 SHORT x LOOP x
34
SYSTEM TROUBLES
A program or database download is in progress. The panel is NOT providing fire protection during the
download. Proper authorities should be notified while a download is in progress so that other means of fire
protection can be supplied.
The DVCs local microphone is in trouble. There is no communication, or paging has been enabled for over 28
seconds and no signal has been received. Investigate whether the mic is plugged into the DVC, or whether
there is a problem with the local mic.
The DVC's local FFT handset is in trouble. There is no communication, or paging has been enabled for over 28
seconds and no signal has been received. Investigate whether the handset is plugged into the DVC, or
whether there is a problem with the handset.
Loops x and x are not responding. The LCM and LEM for those loops must be serviced.
Local initiation of DRILL.
Network initiation of DRILL.
An annunciator has been placed in manual mode.
VESDA Gateway may be damaged.
Communication is lost between the CPU2-3030 or DVC and the network communications module.
More than two panels have been connected to a high-speed network communications module.
The network is in diagnostic mode.
Communication lost between NCM Port x and corresponding node.
An incompatible product exists on this network.
More than 1 fire panel or more than 4 DVCs has been mapped to the NFS2-3030 for Network Display Mode.
Check network mapping and correct.
Multiple paging sources are attempting to page over the NFN, exceeding the limit of one (1). reduce the
number of paging sources to clear this trouble.
This message occurs every day at 11 am if any troubles exist.
Battery backup and/or clock backup is low. Replace battery.
No devices are installed on the system.
The AMPS-24 (main power supply) AC fail address (base plus one) has not been correctly entered or the loop
is not installed. The AMPS-24 is not configured for "Trouble Reporting". All four of the main power supply
addresses are not programmed for MOD TYPE=Monitor and/or TYPE CODE LABEL=Power Monitor and/or
FLASHSCAN=PS Mon.
The panel door is open.
The DVC has allocated all it's phone channels to DAAs but there are still phones ringing in
requesting more channels
There is a communication failure with the DAA onboard power supply. Call Technical Services.
The Primary Amp at address x has failed. Call Technical Services.
The Primary Amp at address x has had a hardware failure. Call Technical Services.
The Audio Circuit of the Primary Amplifier at address x has been overloaded or shorted so the Audio Signal
has been attenuated. Check wiring and source and ensure that there are no shorts.
The Primary Amplifier at address x has overloaded and shut down. Check the total Load calculations fir the
DS-AMP and/or DS-BDA and ensure the total values do not exceed 120 watts.
The DS-BDA at DS-BUS address x (1-4) is drawing more current from the power supply than expected and
has been disabled. Refer to the DVC manual for additional troubleshooting.
Communication loss with printer. Restore power and/or printer's online status.
Add paper.
The database that houses the panel's programming is corrupt. It must be re-downloaded, or all programming
must be cleared and re-entered. Service required.
A user is currently using the panel's programming menus.
The remote display at address x is not responding.
The remote display at address x is in trouble.
The DVC's remote microphone is in trouble. It is installed and supervised, but no signal is coming from it.
Investigate and fix.
Diagnostic test failed. Call Technical Services.
LCM and/or LCD-160 software does not match the version number expected by the panel; and/or the NCM is
not network version 5.0; and/or one or more DAAs has a software revision that does not match other DAA
software revisions. Update software as necessary.
Service required. Call Technical Services.
Table 2.2 System Troubles (3 of 4)
TROUBLE DESCRIPTION
NFS2-3030 Operations Manual — P/N 52546:N1 06/20//2014
System or Point Trouble Event