Read Status
Display
Lines 1 through 6 - Refer to the descriptions in Section 3.2, "Smoke Detector", on page 52.
EQUATION: The logic equation for this logic zone is displayed here
Line 15 - Current time and date.

3.10 Releasing Zone

When a releasing zone address is entered into the Point Select Screen and the ACCEPT soft key is
pressed, the following screen will display:
Display
Lines 9 through 7 - Refer to the descriptions in Section 3.2, "Smoke Detector", on page 52.
Line 9 - DELAY TIME - Gives the delay time setting - a value from 0 to 60 seconds - for this releas-
ing zone.
Line 10 - ABORT SWITCH - Displays the type of abort switch; ULI, IRI, NYC or AHJ.
Line 11 - CROSS ZONE - Displays the cross zone setting; NO, YES, ZONE, or HEAT.
Line 12 - SOAK TIME - Displays the Soak Time setting; 0 to 9999 seconds.
Line 15 - Displays the current time and date.
For further information on Releasing Zones, refer to Appendix B of this manual.
60
L A K E V I E W G E N E R A L H O S P I T A L
S Y S T E M N O R M A L
1 0 : 2 2 : 3 4 A
T U E J A N 2 5 , 2 0 1 1
R E A D A D D R E S S : N 1 2 4 Z R 0 8
A U T O M A T I C
I N A C T I V E
R E L E A S I N G Z O N E N U M B E R 0 8
D E L A Y T I M E : 3 0 S E C O N D S
A B O R T S W I T C H : A H J
C R O S S Z O N E : N O
S O A K T I M E : 3 6 0 0 S E C O N D S
1 0 : 2 2 : 3 4 A
Figure 3.11 Releasing Zone Screen - Read Status
T U E J A N 2 5 , 2 0 1 1
NFS2-3030 Operations Manual — P/N 52546:N1 06/20//2014
Releasing Zone
Z R 0 8
B A C K

Hide quick links: