warning of fires caused by arson, children playing with matches (especially in bedrooms), smoking in bed, and violent explosions (caused by escaping gas, improper storage of Limit-C1-2-2007 flammable materials, etc.). NFS2-640/E Operations Manual — P/N 52743:F1 06/16/2011...
HARSH™, NIS™, and NOTI•FIRE•NET™ are all trademarks; and Acclimate® Plus, FlashScan®, NION®, NOTIFIER®, ONYX®, ONYXWorks®, UniNet®, VeriFire®, and VIEW® are all registered trademarks of Honeywell International Inc.HARSH™, NIS™, and NOTI•FIRE•NET™ are all trademarks; and Acclimate® Plus, FlashScan®, NION®, NOTIFIER®, ONYX®, ONYXWorks®, UniNet®, VeriFire®, and VIEW® are all registered trademarks of Honeywell International Inc.
Page 4
•Brief description of content you think should be improved or corrected •Your suggestion for how to correct/improve documentation Send email messages to: FireSystems.TechPubs@honeywell.com Please note this email address is for documentation feedback only. If you have any technical issues, please contact Technical Services. NFS2-640/E Operations Manual — P/N 52743:F1 06/16/2011...
3.11: Active Trouble Monitor Mode of Operation....................29 3.11.1: How the Control Panel Indicates an Active Trouble Monitor............29 3.11.2: How to Respond to an Active Trouble Monitor ................29 3.12: Output Circuit Trouble Mode of Operation ....................30 3.12.1: Overview ............................30 NFS2-640/E Operations Manual — P/N 52743:F1 06/16/2011...
Page 6
C.3: Using the CRT-2 for Read Status ........................62 C.3.1: Overview ............................62 C.3.2: Accessing Read Status Options......................62 C.3.3: Read Point ............................63 C.3.4: Display Devices in Alarm or Trouble ....................63 C.3.5: Display All Programmed Points .......................64 C.3.6: Step-through History.........................64 NFS2-640/E Operations Manual — P/N 52743:F1 06/16/2011...
Page 7
C.4.6: Clear the Entire History Buffer......................67 C.4.7: Set the Pre-Alarm for Alert or Action....................67 Appendix D: Point and System Troubles Lists ..............68 D.1: Point (Device) Troubles ..........................68 D.2: System Troubles............................69 Index............................72 NFS2-640/E Operations Manual — P/N 52743:F1 06/16/2011...
Escape key appears on the control panel Table 1.1 Typographic Conventions in this Manual NOTE: In this manual, the term NFS2-640 is used to refer to the NFS2-640 and NFS2-640E unless otherwise noted. NFS2-640/E Operations Manual — P/N 52743:F1 06/16/2011...
Security alarm point option with separate audible signal code • Centralized voice paging and audible alarm signaling options • Programmable Control-By-Event control of outputs from individual alarm or supervisory addressable devices • Networks with other FACPs and equipment for large applications. NFS2-640/E Operations Manual — P/N 52743:F1 06/16/2011...
Lights when the proper primary AC power is Always lit with AC power applied. POWER applied. Remains lit while power is applied. Table 2.1 Descriptions of System Status Indicator LEDs (1 of 2) NFS2-640/E Operations Manual — P/N 52743:F1 06/16/2011...
Changes all active LED indicators from flashing to steady • Sends an Acknowledge message to the History buffer and installed printers, CRT-2 terminals, and FDU-80 annunciators • Sends a signal to silence the sounders on the FDU-80 and ACS annunciators NFS2-640/E Operations Manual — P/N 52743:F1 06/16/2011...
Notification Appliance Circuits. DRILL To prevent accidental activation, you must press the key for 2 seconds. When pressed, the DRILL control panel does the following: • Turns on all silenceable NACs NFS2-640/E Operations Manual — P/N 52743:F1 06/16/2011...
NEXT SELECTION PREVIOUS , and SELECTION RECALL LAST ENTRY INCREMENT NUMBER • ENTER • Cursor movement keys: key, key, key, LEFT ARROW RIGHT DOWN • Alphabetic and numeric keys, with selection key LOWER CASE NFS2-640/E Operations Manual — P/N 52743:F1 06/16/2011...
Page 15
Arrow keys – press to move the cursor one place in the direction of the arrow key – press to exit a selection or move the cursor one place to the left Figure 2.2 Programming Keypad NFS2-640/E Operations Manual — P/N 52743:F1 06/16/2011...
S Y S T E M N O R M A L 0 1 : 5 6 P 0 4 1 5 0 8 S a t Figure 3.1 Sample System Normal Message NFS2-640/E Operations Manual — P/N 52743:F1 06/16/2011...
The local sounder will silence and the ACKNOWLEDGE SCROLL DISPLAY FIRE LED will change from flashing to steady. ALARM The control panel will send an acknowledge message to the LCD display, remote annunciators, history buffer, installed printers, and CRT-2s. NFS2-640/E Operations Manual — P/N 52743:F1 06/16/2011...
CO MONITOR* Indicates activation of a CO conventional detector Activates CBE, does not light an indicator at the control panel. Detectors Table 3.1 Fire Alarm Type Codes (1 of 2) NFS2-640/E Operations Manual — P/N 52743:F1 06/16/2011...
The system goes into system trouble when the control panel detects an electrical fault. If no fire alarms exist, the control panel does the following: • Produces a pulsed audible tone • Activates the Trouble relay (TB4) NFS2-640/E Operations Manual — P/N 52743:F1 06/16/2011...
Correct the condition causing the trouble. If the trouble clears, the control panel sends a Clear Trouble message to the History buffer and installed printers FDU-80 annunciators, and CRT-2s. If all troubles clear and no supervisory signals or fire alarms exist, the control panel does the following: NFS2-640/E Operations Manual — P/N 52743:F1 06/16/2011...
Flashes the LED (yellow) SUPERVISORY • Displays one of the Type Codes listed in Table 3.3. • Displays in the status banner on the control panel, along with information specific to ACTIVE the device NFS2-640/E Operations Manual — P/N 52743:F1 06/16/2011...
LED from flashing to steady—regardless of the number of troubles, alarms, and SUPERVISORY supervisory signals. The control panel sends a Supervisory message to the remote annunciators, history buffer, installed printers, and CRT-2s. Correct the condition that activated the supervisory point. NFS2-640/E Operations Manual — P/N 52743:F1 06/16/2011...
The control panel activates a Pre-Alarm Warning if a detector exceeds the programmed Pre-Alarm Alert or Action level. When a detector activates a Pre-Alarm, the control panel does the following: • Pulses the panel sounder • Flashes the ALARM • Activates the Pre-Alarm zone (F9) NFS2-640/E Operations Manual — P/N 52743:F1 06/16/2011...
The Type Code that displays in the Pre-Alarm warning indicates the function of the point that initiates the Pre-Alarm warning. Refer to the Detectors section of Table 3.1 for the Type Codes that can appear in a Pre-Alarm warning, and for descriptions of those Type Codes. NFS2-640/E Operations Manual — P/N 52743:F1 06/16/2011...
TELE PAGE Performs function of Page Button on FFT-7 Allows remote paging to a fire area ABORT SWITCH Indicates Active at the panel Aborts activation of a releasing zone Table 3.4 Non-Alarm Type Codes NFS2-640/E Operations Manual — P/N 52743:F1 06/16/2011...
Latches the control panel in CO alarm. (You can not return the control panel to normal operation until you correct the CO alarm condition and reset the control panel) • Initiates any Control-By-Event actions—activiates ZF18 NFS2-640/E Operations Manual — P/N 52743:F1 06/16/2011...
CBE, CO alarm activates special function zone FC and sixth CBE zone only (sixth CBE zone programmable via VeriFire Tools) Table 3.5 CO Alarm Type Codes (1 of 2) NFS2-640/E Operations Manual — P/N 52743:F1 06/16/2011...
The control panel sends an Acknowledge message to the History buffer and installed printers, FDU-80 annunciators, and CRT-2s. Check the trouble message for the location and type of trouble. Correct the condition causing the trouble. NFS2-640/E Operations Manual — P/N 52743:F1 06/16/2011...
ACKNOWLEDGED. * Type Code is Control Module type code only. ** Type Code is NAC Circuit type code only. Table 3.7 Control Module and NAC Circuit Trouble Type Codes NFS2-640/E Operations Manual — P/N 52743:F1 06/16/2011...
When the trouble condition is corrected, the panel will return to normal operation (indicated by the “System Normal” message). The control panel sends a “System Normal” message to the LCD display, History buffer and installed printers, FDU-80 annunciators, and CRT-2s. NFS2-640/E Operations Manual — P/N 52743:F1 06/16/2011...
(0-300 seconds) when a fire alarm occurs. A Silence Inhibit Timer starts at the first fire alarm. Subsequent alarms will not restart the timer until the alarm condition is completely resolved and a panel reset is performed. NFS2-640/E Operations Manual — P/N 52743:F1 06/16/2011...
The trouble will display on the panel as a Style 6 trouble until you correct the condition. Style 7 configuration of the SLC requires the use of ISO-X isolator modules. NFS2-640/E Operations Manual — P/N 52743:F1 06/16/2011...
“How to View Read Status for a Releasing Zone (R0-R9)” on page 40 System Functions “How to Read Status for System Functions” on page 40 Annunciator Selections “How to Read Status for Annunciator Selections” on page 41 NFS2-640/E Operations Manual — P/N 52743:F1 06/16/2011...
Page 36
Alarm sensitivity level Alarm Verification Time Pre-Alarm sensitivity level (in seconds) Alarm Verification selection: V on; * off Multidetector selection: A, B, C, or * (not selected) Figure 4.1 Sample Detector Read Status Display NFS2-640/E Operations Manual — P/N 52743:F1 06/16/2011...
Page 37
Switch Inhibit: I selected, * not selected Walk Test selection: Silenceable: O = selected, * = not selected (default) W selected for Walk Test * not selected Figure 4.2 Sample Control/Relay or Monitor Module Read Status Display NFS2-640/E Operations Manual — P/N 52743:F1 06/16/2011...
Page 38
CBE List Only the first zone in the NAC’s CBE list will be displayed here. • Device Address The address of the NAC (01-04) • Switch Inhibit A selection for disabling the switch function for the control/relay or transponder output circuit. (I=on; *=off). NFS2-640/E Operations Manual — P/N 52743:F1 06/16/2011...
Page 39
M A R C H T I M E Code Type selection Indicates Special Zone F8 for Special Zone F8 NOTE: Special Function Zones FA, FB, and FC are represented in VeriFire Tools as ZF10, ZF16, and ZF18, respectively. NFS2-640/E Operations Manual — P/N 52743:F1 06/16/2011...
Page 40
NO – No FDU-80 supervision. AC_DLY=N Delays AC loss reporting YES - AC loss reporting is delayed for approximately 3 hours. NO - No AC loss delay. Table 4.1 System Function Parameters (1 of 2) NFS2-640/E Operations Manual — P/N 52743:F1 06/16/2011...
Page 41
A N N U N S E L E C T I O N 4 : A 2 9 = * A 3 0 = * A 3 1 = * A 3 2 = * Figure 4.9 Annunciator Selections 3 and 4 Screens NFS2-640/E Operations Manual — P/N 52743:F1 06/16/2011...
Page 42
P R T _ B A U D : 2 C H A R G E R : Y Figure 4.13 System Function Selection 8 Screen NOTE: Please refer to the Verifire Tools help file for information on programming the above screen. NFS2-640/E Operations Manual — P/N 52743:F1 06/16/2011...
Page 43
Annunciators set to annunciator address 1 (A1) display the status of detectors 1-64 on SLC 1 (ACS Selection Group H) • Annunciators set to annunciator address 2 (A2) display the status of intelligent modules 1-64 on SLC-1 (ACS Selection Group C). NFS2-640/E Operations Manual — P/N 52743:F1 06/16/2011...
Page 44
B a t t e r y V o l t a g e : 2 7 . 4 8 V C h a r g e r C u r r e n t : 0 0 . 0 6 A Figure 4.15 Battery Levels NFS2-640/E Operations Manual — P/N 52743:F1 06/16/2011...
G R O U N D F A U L T 0 1 : 4 6 P 0 4 1 5 0 8 T u e Time and date of the event Figure 4.17 Sample Trouble Event Display NFS2-640/E Operations Manual — P/N 52743:F1 06/16/2011...
NOTE: Before printing, make sure your control panel is connected to a compatible printer and the printer is configured according to the manufacturer’s specifications, and that the correct baud rate is selected at the panel. NFS2-640/E Operations Manual — P/N 52743:F1 06/16/2011...
Page 47
A sample printout of two alarm events in the History buffer using the Print Alarm History option. ********************ALARM HISTORY START **************************************** ALARM: SMOKE (ION) DETECTOR ADDR 1D075 Z002 02:28P 012208 1D075 ALARM: SMOKE (ION) DETECTOR ADDR 1D076 Z002 02:28P 012208 1D076 ******************* PRINT END **************************************** NFS2-640/E Operations Manual — P/N 52743:F1 06/16/2011...
“How to Print Alarm History” on page 47 Read Hidden History “How to View Read Status for Event History” on page 45 Print Hidden History “How to Print Event History” on page 47 Table 4.3 Hidden History Selections NFS2-640/E Operations Manual — P/N 52743:F1 06/16/2011...
Soak Timer Automatically shuts off the releasing device after a preprogrammed period of time. Select 0001-9999 seconds for a Soak Timer or 0000 seconds for no Soak Timer. Table A.1 Releasing Options NFS2-640/E Operations Manual — P/N 52743:F1 06/16/2011...
F R O N T H A L L W A Y N O . 3 R 1 _ _ _ _ _ _ _ _ I * * B 0 3 CBE list = R1 NFS2-640/E Operations Manual — P/N 52743:F1 06/16/2011...
Page 51
• An alarm from 2D102 and 2D103 – detectors mapped to different zones, but both list ZR1 in their CBE. Cross=H Activation of heat detector 2D104 and one smoke detector (2D101, 2D102, or 2D103). Table A.2 Example of Cross Zone Selections NFS2-640/E Operations Manual — P/N 52743:F1 06/16/2011...
O N = 0 7 : 0 0 O F F = 1 5 : 0 0 D A Y S = S M T W T F * H F 0 5 ON time for Zone F5 devices that list Day-of-week selections OFF time for devices (H=holiday selected) that list F5 Figure A.4 Sample Read Status for Time Function NFS2-640/E Operations Manual — P/N 52743:F1 06/16/2011...
Control a specific date of year Input up to nine date in the Holiday selection screen for Special Zone F7, then list zone F7 (Holiday) in the CBE of a device. Table A.3 Time Control Applications NFS2-640/E Operations Manual — P/N 52743:F1 06/16/2011...
O F F C O D I N G F U N C T I O N C O D E T Y P E M A R C H T I M E F 0 8 Coding selection Zone F08 Figure A.6 Sample Read Status for Coding Function NFS2-640/E Operations Manual — P/N 52743:F1 06/16/2011...
An illustration of Presignal and PAS timing. Presignal Delay Timer (60-180) PAS (15s) If PAS=Y, alarm activates outputs if not acknowledged Initial alarm Alarm activates outputs, annunciation if panel is not reset. Figure A.7 Presignal and PAS Time NFS2-640/E Operations Manual — P/N 52743:F1 06/16/2011...
The Manual Evacuate screen and Alarm screen display alternately at 3-second intervals. If the Presignal Delay Timer reaches its programmed value, without operator intervention, the control panel activates all outputs programmed to F0. NFS2-640/E Operations Manual — P/N 52743:F1 06/16/2011...
The Manual Evacuate screen and Alarm screen display alternately at 3-second intervals. If the Presignal Delay Timer reaches its programmed value, without operator intervention, the control panel activates all outputs programmed to F0. NFS2-640/E Operations Manual — P/N 52743:F1 06/16/2011...
30 seconds). Each detector includes a Verification Counter, which displays the number of times that a detector entered verification but did not time-out to alarm. The Verification Counter increments to 99 and holds. Table B.1 Intelligent Detector Functions NFS2-640/E Operations Manual — P/N 52743:F1 06/16/2011...
• Step through the History buffer event by event. • Display the entire History buffer. • Step through Alarm History • Display the entire Alarm History Table C.1 Local Terminal Mode Functions (1 of 2) NFS2-640/E Operations Manual — P/N 52743:F1 06/16/2011...
Requirements: Use with UL ITE-listed terminals, including personal computers with the VeriFire™ Tools or terminal emulation software. Intended for terminals connected through modems, including FSK modems connected through a public switched telephone network. NFS2-640/E Operations Manual — P/N 52743:F1 06/16/2011...
Turn on the CRT-2, which is connected to the control panel. Press the Read Status function key. The control panel displays the “Read Status” menu options: Rd Point=1, Rd Alm/Tbl=2, All Points=3, Hist:Step=4/All=5, Ala-Hist:Step=6/All=7 NFS2-640/E Operations Manual — P/N 52743:F1 06/16/2011...
DETECTOR ADDR 1D002 Z002 000%A6 6 ** 1D002 C.3.4 Display Devices in Alarm or Trouble From the “Read Status” menu, select option 2 - Read Alarms/Troubles. The CRT-2 will display the alarm and trouble history. NFS2-640/E Operations Manual — P/N 52743:F1 06/16/2011...
03:20P 041408 1M065 ALARM: SMOKE (ION) DETECTOR ADDR 1D129 03:20P 041408 1M065 Step through the Alarm History buffer one event at a time by pressing the Next F5 or Prior F6 function keys. NFS2-640/E Operations Manual — P/N 52743:F1 06/16/2011...
CRT-2. Five asterisks will appear in place of the password. Press <1><1><1><1><1>< > ENTER ***** The Alter Status Options menu appears. 1=Disable 2=Alarm/Prealarm 3=Clear Verification 4=Clear History 5=Alert/Action From the Alter Status Options menu, you can select 1-5. NFS2-640/E Operations Manual — P/N 52743:F1 06/16/2011...
Alarm/Prealarm level 08:29A Tue 04/15/08 D102 sens. at level 5, Prealarm at level 3, Enter AxPx to change, Esc. to Abort D102 now set at new Alarm level 5 and new Pre-alarm level 2 NFS2-640/E Operations Manual — P/N 52743:F1 06/16/2011...
“Alert” to “Action” as follows: Press <5>< > ENTER Set Pre-alarm Alert (NO)/Action(YES). Type N or Y then Enter STATUS CHANGE Change Alert/Action 08:29A Tue 04/15/08 Press <Y>< > ENTER Pre-alarm now set for ACTION NFS2-640/E Operations Manual — P/N 52743:F1 06/16/2011...
Check the connections from the module to the input or output device to which it is wired. SHORT ON x. There is a short on speaker circuit x. Locate the short and fix. Table D.1 Point (Device) Troubles (1 of 2) NFS2-640/E Operations Manual — P/N 52743:F1 06/16/2011...
Technical Services. DVC FFT Riser TBL DVC DBASE INCOMPAT The application or database version is incompatible. The correct application or database version must be downloaded. Table D.2 System Troubles NFS2-640/E Operations Manual — P/N 52743:F1 06/16/2011...
Page 70
Install SLC and run autoprogram. PANEL DOOR OPEN The panel door is open. Close door. POWER SUPPLY COMM There has been a communication failure with the power Service is required. FAIL supply. Table D.2 System Troubles NFS2-640/E Operations Manual — P/N 52743:F1 06/16/2011...
Page 71
The UDACT is in trouble. Determine if the UDACT is functional and wired correctly. * This trouble may be fire panel or backup battery related. Test and replace backup batteries if necessary/ Table D.2 System Troubles NFS2-640/E Operations Manual — P/N 52743:F1 06/16/2011...
Page 75
Manufacturer's Return Material Authorization form. The replacement part shall come from Manufacturer's stock and may be new or refurbished. THE FOREGOING IS DISTRIBUTOR'S SOLE AND EXCLUSIVE REMEDY IN THE EVENT OF A WARRANTY CLAIM. Warn-HL-08-2009.fm NFS2-640/E Operations Manual — P/N 52743:F1 06/16/2011...
Page 76
World Headquarters 12 Clintonville Road Northford, CT 06472-1610 USA 203-484-7161 fax 203-484-7118 www.notifier.com...