Active Event - Notifier NFS2-3030 Operation Manual

Fire alarm control panel
Hide thumbs Also See for NFS2-3030:
Table of Contents

Advertisement

Active Event

2.13 Active Event
2.13.1 How the Control Panel Indicates an Active Fire Control
Point
A point with a Type ID of
mal operating automatic functions.
Activation of a
Initiates the monitor module Control-by-Event
Send a message to the panel display, History buffer, installed printer and annunciators
Does NOT light an indicator at the control panel
Displays ACTIVE in the upper left corner of the LCD, as well as a
and other information specific to the device
2.13.2 How the Control Panel Indicates an Active Non-fire Point
A point with a Type ID of
-
NON
FIRE
the panel LCD. Activation of a
on the control panel. For example, you can program a
lower setting when activated. In this case, when the point activates the control panel activates the
point's CBE to turn the lights down without any audio or visual indication on the control panel.
2.14 Operation of Special System Timers, Presignal, and PAS
2.14.1 System (Panel) Timers
There are user-programmable time delays for four specific functions: Alarm Verification, AC Fail,
Silence Inhibit, and Auto Silence. Refer to this panel's programming manual for instructions on
viewing or modifying these values. (They may be viewed only in programming mode.)
Alarm Verification Timer (
A timer that directs the control panel to ignore a fire alarm for a smoke detector, programmed for
Alarm Verification, while the Alarm Verification Timer is counting. The timer value can be set
from 0-60 seconds, and may not exceed 30 seconds for ULC installations. Table 2.3 contains a
summary of how the Alarm Verification Timer works.
A second fire alarm occurs while the
Alarm Verification Timer is counting
The Alarm Verification Timer elapses and
a fire alarm still exists
The Alarm Verification Timer expires and
a fire alarm no longer exists
AC Fail Delay Timer
This timer delays the time from the start of AC failure to when the trouble is reported. The timer
value may be set to none, or from 1-12 hours. A value of "none" will cause immediate notification.
The onboard trouble relay and municipal box output will activate when the countdown is complete.
Note that this panel notifies the central station communicator as soon as AC failure occurs, and the
central station communicator follows its own programmed schedule for reporting the failure.
NFS2-3030 Operations Manual — P/N 52546:N1 06/20//2014
FIRE CONTROL
point causes the control panel to do the following:
FIRE CONTROL
-
is used for energy management or other non-fire situations.
NON
FIRE
point operation does not affect control panel operation, nor does it display a message at
-
NON
FIRE
V E R I F Y T I M E
If this event occurs
Table 2.3 Alarm Verification Timer Operation
is used for air handler shutdown, intended to override nor-
point activates CBE—but does not cause any indication
-
point to turn lights in a zone to a
NON
FIRE
)
The control panel does this
Ignores the Alarm Verification Timer and alarms are
reported by the panel for both detectors.
Activates the fire alarm
The control panel returns to normal operation and
increments the verification counter
Operation of the Control Panel
Type Code
FIRE CONTROL
49