Table 17 - Interface Diagnostic Items (continued)
Code
Event
359
DHCP Rebind
360
DHCP Release
361
Net Sent Reset
362
Net I/O Open
363
Net I/O Idle
364
Net I/O Close
365
Net I/O Timeout
366
Net I/O Abort
367
PCCC I/O Open
368
PCCC I/O Close
369
PCCC I/O Timeout
370
Msg Ctrl Open
371
Msg Ctrl Close
372
Msg Ctrl Timeout
375
Net Ring Up
376
Net Ring Down
Rockwell Automation Publication 750COM-UM009A-EN-P - May 2017
Troubleshooting
Description
The interface rebinded its network address lease with
the DHCP Server.
The interface network address lease expired.
The interface received a reset command from the
network.
The I/O connection from the network to the interface has
been opened.
The interface received I/O connection 'idle' packets from
the network.
The I/O connection from the network to the interface
was closed.
The interface I/O connection has timed out.
The interface I/O connection was aborted because the
datalink configuration was changed.
The interface began receiving PCCC control messages
after the PCCC Control Timeout was set to a nonzero
value.
The device that sends PCCC control messages to the
interface (for example, the Control Bar feature in CCW)
has set the PCCC Control Timeout to zero.
The interface has not received a PCCC control message
before the PCCC Control Timeout.
The timeout attribute in the CIP-based network
Assembly Object was set to a nonzero value. This allows
control messages to be sent to the interface via the CIP-
based network Assembly Object.
The timeout attribute in the CIP-based network
Assembly Object was set to zero, disallowing control
messages to be sent to the interface via the CIP-based
network Assembly Object.
The interface has not received a control message via the
CIP-based network Assembly Object before the object
timeout attribute triggered.
The Device Level Ring (DLR) status is Normal.
The Device Level Ring (DLR) status is Faulted.
Chapter 6
117