Allen-Bradley PowerFlex 755T User Manual page 129

Powerflex 750-series drives with totalforce control built-in ethernet/ip adapter
Hide thumbs Also See for PowerFlex 755T:
Table of Contents

Advertisement

Table 25 - Port 0: Parameter List (continued)
No.
Display Name
Extended Name
Description
360
Comm Flt Action
Communication Fault Action
Sets the action that the communication interface and drive take when I/O
communication is disrupted. When communication is re-established, the drive
automatically receives the logic command, reference, and datalinks over the network
again.
'Fault' (0) – The response is a major fault. The drive stops modulating, the motor coasts
to a stop, and a fault reset is required to resume operation.
'Stop' (1) – The response is to stop in the way set by the active stop mode.
'Zero Data' (2) – The response is to continue operating, but to put zeros in the logic
command, reference, and datalinks.
'Hold Last' (3) – The response is to continue operating, and to use the last values in the
logic command, reference, and datalinks.
'Send Flt Cfg' (4) – The response is to continue operating, but to use the logic command
that is specified in parameter
[Flt Cfg Ref]. The drive also uses the values in parameters
Cfg DL 16] in the parameters consuming data from those datalinks
ATTENTION: Take precautions to help maintain that the setting of this parameter does not create a risk of injury or equipment damage. When
commissioning the drive, verify that your system responds correctly to various situations (for example, a disconnected cable).
361
Idle Flt Action
Idle Fault Action
Sets the action that the communication interface and drive take when the controller
leaves the run mode (faulted or in program mode). When the controller returns to the
Run mode, the drive automatically receives the logic command, reference, and datalinks
over the network again.
'Fault' (0) – The response is a major fault. The drive stops modulating, the motor coasts
to a stop, and a fault reset is required to resume operation.
'Stop' (1) – The response is to stop in the way set by the active stop mode.
'Zero Data' (2) – The response is to continue operating, but to put zeros in the logic
command, reference, and datalinks.
'Hold Last' (3) – The response is to continue operating, and to use the last values in the
logic command, reference, and datalinks.
'Send Flt Cfg' (4) – The response is to continue operating, but to use the logic command
that is specified in parameter
[Flt Cfg Ref]. The drive also uses the values in parameters
Cfg DL 16] in the parameters consuming data from those datalinks
ATTENTION: Take precautions to help maintain that the setting of this parameter does not create a risk of injury or equipment damage. When
commissioning the drive, verify that your system responds correctly to various situations (for example, place the controller in program mode).
365
[Flt Cfg Logic] and the reference that is specified in
370
[Flt Cfg DL 01]...
364
[Flt Cfg Logic] and the reference that is specified in
370
[Flt Cfg DL
Rockwell Automation Publication 750COM-UM009A-EN-P - May 2017
Values
Default:
0 = 'Fault'
Options:
0 = 'Fault'
1 = 'Stop'
2 = 'Zero Data'
3 = 'Hold Last'
4 = 'Send Flt Cfg'
365
385
[Flt
Default:
0 = 'Fault'
Options:
0 = 'Fault'
1 = 'Stop'
2 = 'Zero Data'
3 = 'Hold Last'
4 = 'Send Flt Cfg'
365
01]...385
[Flt
Interface Parameters
Appendix C
RW
32-bit
0
Integer
RW
32-bit
0
Integer
131