Viewing And Clearing Events - Allen-Bradley PowerFlex 755T User Manual

Powerflex 750-series drives with totalforce control built-in ethernet/ip adapter
Hide thumbs Also See for PowerFlex 755T:
Table of Contents

Advertisement

Chapter 6
Troubleshooting

Viewing and Clearing Events

116
Table 16 - Interface Diagnostic Items (continued)
No.
Name
68
Net Addr Sw
69
MDIX Status
70
Net Heap Avail
The interface has an event queue to record significant events that occur in the
operation of the interface. When such an event occurs, an entry consisting of
the numeric code of the event and a time stamp is put into the event queue. You
can view the event queue using CCW. The event queue cannot be viewed using
the HIM.
The event queue can contain up to 100 entries, which are stored in nonvolatile
storage (NVS). Eventually the event queue becomes full, since its contents are
retained through power cycles and resets. At that point, a new entry replaces
the oldest entry. Only an event queue clear operation clears the event queue
contents.
Many events in the event queue occur under normal operation. If you
encounter unexpected communication problems, the events can help you or
Allen-Bradley® personnel troubleshoot the problem. The following events can
appear in the event queue.
Table 17 - Interface Diagnostic Items
Code
Event
350
Net LNK1 Up
351
Net LNK1 Down
352
Net LNK2 Up
353
Net LNK2 Down
354
Net Dup Address
355
Invalid Net Cfg
356
BOOTP Response
357
DHCP Response
358
DHCP Renew
Rockwell Automation Publication 750COM-UM009A-EN-P - May 2017
Description
The present value of the interface node address (rotary) switches.
Indicates the type of cable that is connected to the interface ports.
P1 = ENET1 network port and P2 = ENET2 network port.
Bit 0 - P1 Normal
Bit 1 - P1 Swapped
Bit 2 - P2 Normal
Bit 3 - P2 Swapped
The amount of data memory available to the network communication firmware
for dynamic (runtime) memory allocations.
Description
The interface established a network link on its ENET1
network port.
The interface lost the network link on its ENET1 network
port.
The interface established a network link on its ENET2
network port.
The interface lost the network link on its ENET2 network
port.
Another device having the same IP address as the
interface was detected on the network.
The interface network address configuration parameters
are invalid, or the network address that is provided by
the BOOTP or DHCP server is invalid.
The interface received a response to its BOOTP request.
The interface received a response to its DHCP request.
The interface renewed its network address lease with
the DHCP Server.

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Powerflex 755tlPowerflex 755trPowerflex 755tm