Appendix C
Interface Parameters
Table 25 - Port 0: Parameter List (continued)
No.
Display Name
Extended Name
Description
363
Msg Flt Action
Message Fault Action
Sets the action that the interface and drive take when explicit messaging control (only
via PCCC or the CIP Assembly Object) is disrupted. When explicit messaging control is re-
established, the drive automatically receives the logic command, reference, and
datalinks over the network again.
'Fault' (0) – The response is a major fault. The drive stops modulating, the motor coasts
to a stop, and a fault reset is required to resume operation.
'Stop' (1) – The response is to stop in the way set by the active stop mode.
'Zero Data' (2) – The response is to continue operating, but to put zeros in the logic
command, reference, and datalinks.
'Hold Last' (3) – The response is to continue operating, and to use the last values in the
logic command, reference, and datalinks.
'Send Flt Cfg' (4) – The response is to continue operating, but to use the logic command
that is specified in parameter
[Flt Cfg Ref]. The drive also uses the values in parameters
Cfg DL 16] in the parameters consuming data from those datalinks.
ATTENTION: Take precautions to help maintain that the setting of this parameter does not create a risk of injury or equipment damage. When
commissioning the drive, verify that your system responds correctly to various situations (for example, a disconnected cable).
364
Flt Cfg Logic
Fault Configuration Logic
Set the logic command for the drive if any of the following is true:
360
[Comm Flt Action] is set to 4 'Send Flt Cfg' and I/O communication are disrupted.
361
[Idle Flt Action] is set to 4 'Send Flt Cfg' and the controller leaves the run mode.
362 [Peer Flt Action] is set to 4 'Send Flt Cfg' and Peer I/O communication are disrupted.
363
[Msg Flt Action] is set to 4 'Send Flt Cfg' and Explicit Messaging for drive control is disrupted.
Options
Default 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0
Bit
31 30 29 28 27 26 25 24 23 22 21 20 19 18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
Note: The first bit table is for systems that contain both an inverter and a converter or only an inverter. The second bit table is for systems that contain ONLY a converter.
Options
Default 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0
Bit
31 30 29 28 27 26 25 24 23 22 21 20 19 18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
132
364
[Flt Cfg Logic] and the reference that is specified in
370
[Flt Cfg DL 01]...
Rockwell Automation Publication 750COM-UM009A-EN-P - May 2017
Values
Default:
0 = 'Fault'
Options:
0 = 'Fault'
1 = 'Stop'
2 = 'Zero Data'
3 = 'Hold Last'
4 = 'Send Flt Cfg'
365
385
[Flt
RW
32-bit
0
Integer
RW
Bit
0