Chapter 2
Configure the Interface
28
IMPORTANT Regardless of the method that is used to set the interface IP address, each
node on the EtherNet/IP network must have a unique IP address. To change
an IP address, you must set the new value and then remove and reapply
power to (or reset) the interface.
Settings
Description
001...254
The interface uses the rotary switch settings for the IP address (192.168.1.xxx, where xxx = the
rotary switch settings). The value that is stored in 0: 300 - [Net Addr Sel] is automatically
ignored.
888
Resets the interface IP address and other EtherNet/IP communication settings to factory
defaults. Thereafter, the drive must be powered down, the switches set to a correct value
(001...254 or 999), and then the drive must be powered up again to accept the new address.
999
Disables the rotary switches, and requires using one of the following:
• 0:300 - [Net Addr Sel] selects the source for the interface IP address, which is one of the
following:
– Interface Parameters
– BOOTP server (default)
– DHCP server firmware
Any other
Reserved.
setting
The switch settings can be verified by viewing Port 0 Diagnostic Item number
68
(page
113) with any of the following drive configuration tools:
• PowerFlex 20-HIM-A6 or 20-HIM-C6S HIM
• Connected Components Workbench software, release 10 or later
Also, you can use 0:301 - [Net Addr Src], a read-only parameter, to verify the
active setting for 0:300 - [Net Addr Sel].
Rockwell Automation Publication 750COM-UM009A-EN-P - May 2017