jacarta interSeptor Pro User Manual page 16

Environmental monitoring system for data centers, server rooms, racks. 8-port, 16-port, 24-port versions
Hide thumbs Also See for interSeptor Pro:
Table of Contents

Advertisement

interSeptor Pro
Configure the following settings for a new device:
Device Name: Enter the device name.
Device Status: Select Auto from the drop down menu to enable the device or Disabled to
disable.
Display: Select Enable from the drop down menu to display the device in the Comprehensive
View and Java display or Disabled to disable.
Set Point: Enter a temperature or humidity value over or under which an alarm will be
triggered. You can enter values for warning or critical levels. The valid ranges are as follows:
Temperature: -15° C (5 ° F) to 65 ° C (149 ° F)
Humidity: 5% to 95%
Hysteresis: A sensors value could be floating around the configured threshold, triggering
multiple alarms. Setting the hysteresis will help to prevent the alarm being constantly
activated and deactivated in this situation.
For example, if the low warning threshold point is 20 and hysteresis is 3, then the alarm will
activate when the value reaches 20 but will not deactivate until the value reaches 23.
For the contact alarm sensors, the hysteresis can be used to adjust the sensitivity of an alarm.
The alarm will be active or inactive only after the alarm stays in the same state of the
hysteresis value (in seconds).
Calibration Offset: If the measurement value of a sensor does not comply with the actual
environment for whatever reason, a calibration offset value can be set to adjust the final
sensor reading.
For example, if a sensor reports 43% humidity in an environment where humidity is at 45%,
you can set the humidity offset to 2% so the sensor can adjust its final reading.
Alarm Type: If an alarm is connected to the interSeptor Pro, select from Normal Open,
Normal Close or Disabled.
Normal Open & Normal Close are used for a two wire detector that emulates an open/close
state.
Event Output: Select from D01 or D02 as the event output when a digital output is connected.
Scroll down to the bottom of the screen to configure output control settings. Check Show
advanced parameters and the following will display: