mA I/O Parameters (P200 - P220)

These parameters are specific to the use of the mA output. Refer to
page 57 for details.
mA output 1 is physically located at terminals 21/22 on the main board
mA outputs 2 and 3, and inputs 1 and 2 are physically located on the optional mA
I/O board which is mounted onto the main board.
In the case of assigning mA input and output functions to PID control, the following
correlation exist:
PID control 1
PID control 2
P200
mA Output Range
Sets the mA range for the output selected, outputs 1 to 3 (P200 - 01 to - 03).
Entry:
1 = 0 - 20 mA
f
2 = 4 - 20 mA
P201
mA Output Function
Assigns the mA output function for the output selected, outputs 1 to 3 (P201 - 01 to - 03)
Entry:
f
1 = rate
2 = load
3 = speed
4 = PID control output*
* valid for outputs 2 and 3, only if PID system (P400) is enabled
P204
mA Output Average
Sets the averaging period, in seconds, for the rate output for output 1 only.
The instantaneous mA values are averaged for the set period, and then the average value
is output during the next period while a new average is being calculated.
Entry:
f
0 = OFF
1 – 999 = averaging period
Page 110
mA input
Milltronics BW500 - INSTRUCTION MANUAL
mA output
1
2
mA Output
on
2
3
7ML19985DK03