Appendix B Limits and Performance Data
Appendix B Limits and Performance Data
Limits of the Linking Device on HSE
Maximum Limits
Maximum Limits of the Linking Device on HSE
Configured HSE sessions
Configured HSE VCRs
Automatic HSE sessions
Automatic HSE VCRs
H1-H1 republishings
Performance of HSE communication
For System 800xA SV5.1 onwards, Signal Transfer between HSE and H1 is able to
handle a maximum of 160 signals per second between all four H1 links and the HSE
network, while 4*16 client/server connections can be used parallel. For availability
with other system environments, check corresponding system release notes.
In ABB system environments, the configuration tools Fieldbus Builder
FOUNDATION Fieldbus and Control Builder F will take these limits into
account automatically, depending on the capability of the system version and if
not noted otherwise.
3BDD011677-600 A
Limits of the Linking Device on HSE
64
400
32
256
64