3.4.3.
22
COM600 series, Version 5.0
IEC 60870-5-103 Master (OPC) User's Manual
Configuring IEC103 Channel properties
The IEC103 Channel properties that can be configured and value ranges for them can
be found in Table 3.4.3-1. The actual configuration by using SAB600 is performed as
described in 3.4.1, General information about configuring objects.
Table 3.4.3-1 IEC103 Channel properties
Name
Value or Value range/ Default
Basic
In Use
In Use
Not In Use
Default: In Use
Communication
Port
Bit Rate
300 bits/s 600 bits/s 1200 bits/s
2400 bits/s 4800 bits/s 9600
bits/s 19200 bits/s
Default: 19200 bits/s
Communication Port
COM1...COM4
Default: COM1
Parity
No parity check
Odd parity
Even parity
Default: No parity check
Communication
Control
Carrier Blocking
Carrier Detect ignored
Carrier Detect must be set
Default: Carrier Detect must be
set
CTS Delay
1...65535
Default: 50
Header Timeout
0...65535
Default: 2000
Ignore the DFC bit
True
False
Default: False
Description
Controls whether the device communica-
tion is initially in use or not.
Transmission rate used on the line
Serial port used by the IEC 60870-5-103
protocol
Specifies the used parity check.
Usage of DCD signal of the serial port
CTS waiting delay in milliseconds
Maximum waiting time of a link layer
response in milliseconds
Ignore the DFC bit. If true, master contin-
ues polling normally. If false, master sends
the 'request status of link' until the remote
station clears the DFC bit.
1MRS752278