Configuring DNP Serial IED properties

Table 3.4.4-1 lists the configurable properties for DNP Serial IED and value ranges for
these properties. The actual configuration by using the SAB600 is performed as described
in 3.2, Overview of configuration.
Table 3.4.4-1 DNP Serial IED properties
Name
Value/Value range
Basic
Diagnostics Enabled
True
False
Default: False
In Use
In use
Not in use
Default: In use
Subset
Subset 2
Subset 3
Default: Subset 2
Addresses
Master Address
0...65535
Default: 1
Slave Address
0...65535
Default: 1
Communication
Control
Confirmation
0...600
Timeout
Default: 10
Sending Messages
True
False
Default: True
Transport Layer
0...600
Timeout
Default: 10
Use Variations
True
False
Default: True
Description
Specifies whether diagnostic AE events
are sent for the station.
Defines if the IED is in use or not.
Defines the subset level that is currently
used.
The station address of the master station.
The station address of the slave station.
The maximum time in seconds that the
slave station waits for an application layer
confirmation from the master.
Sending messages while waiting for a
confirmation.
The maximum time in seconds that the
transport layer is allowed to assemble one
application message fragment.
Variations in response messages.
25