Supplement
Coding of the status byte associated with the PA output value
Status
Description acc. to Profibus
code
standard
0x00
bad - non-specific
0x04
bad - configuration error
0x0C
bad - sensor failure
0x10
bad - sensor failure
0x1f
bad - out of service constant
0x44
uncertain - last unstable value
0x48
uncertain substitute set
0x4c
uncertain - initial value
0x51
uncertain - sensor; conversion not
accurate - low limited
0x52
uncertain - sensor; conversion not
accurate - high limited
0x80
good (non-cascade) - OK
0x84
good (non-cascade) – active block
alarm
0x89
good (non-cascade) – active ad-
visory alarm – low limited
0x8a
good (non-cascade) – active ad-
visory alarm – high limited
0x8d
good (non-cascade) – active crit-
ical alarm – low limited
0x8e
good (non-cascade) – active crit-
ical alarm – high limited
52
possible cause
Flash-Update active
Adjustment error
l
Configuration error with PV-Scale (PV-Span too small)
l
Unit irregularity
l
Error in the linearization table
l
Hardware error
l
Converter error
l
Leakage pulse error
l
Trigger error
l
Measured value generation error
l
Temperature measurement error
l
"Out of Service" mode switched on
Failsafe replacement value (Failsafe-Mode = "Last value" and already
valid measured value since switching on)
Switch on simulation
l
Failsafe replacement value (Failsafe-Mode = "Fsafe value")
l
Failsafe replacement value (Failsafe-Mode = "Last valid value" and no
valid measured value since switching on)
Sensor value < lower limit
Sensor value > upper limit
OK
Static revision (FB, TB) changed (10sec long active after the parameter
of the static category was written)
Lo-Alarm
Hi-Alarm
Lo-Lo-Alarm
Hi-Hi-Alarm
VEGABAR 53 - Profibus PA