Select application "Level
measurement"
Select adjustment unit/den-
sity unit
VEGABAR 53 - Profibus PA
Setup with the indicating and adjustment module PLICSCOM
VEGABAR 53 is preset to application "Process pressure
measurement". Proceed as follows when switching over to
application "Level measurement":
1 Push the [OK] button in the measured value display, the
menu overview is displayed.
2 Select the menu Service with "[–>]" and confirm with [OK].
Basic adjustment
Display
Diagnostics
▶
Service
Info
3 Select the menu item "Application" with [–>] and edit with
[OK].
Warning:
Note the warning: "Output can change".
4 Select "OK" with [–>] "OK" and confirm with [OK].
5 Select "Level" from the list and confirm with [OK].
To switch over to another adjustment unit (in the example from
bar to mbar), proceed as follows:
1 Push the [OK] button in the measured value display, the
menu overview is displayed.
▶
Basic adjustment
Display
Diagnostics
Service
Info
2 Confirm the menu "Basic adjustment" with [OK], the
menu item "Units of measurement" will be displayed.
Units of measurement
bar
3 Activate the selection with [OK] and select the requested
unit with [–>] (in the example mbar).
Selection options: mbar, bar, psi, Pa, kPa, MPa, inHg, mmHg, inH
6)
mmH
O, mm, cm, m, in, ft.
2
6)
O,
2
27