Setup with the indicating and adjustment module PLICSCOM
Select the adjustment unit
Carry out position correction
24
PLICSCOM enables the adjustment without filling or pressure.
You can carry out the settings in the workshop without the
instrument having to be installed.
In addition to the menu items for zero/span adjustment, the
current measured value is displayed.
To switch over to another adjustment unit (in the example from
bar to mbar), proceed as follows:
1 Push the [OK] button in the measured value display, the
menu overview is displayed.
Basic adjustment
Display
Diagnostics
Service
Info
2 Confirm the menu "Basic adjustment" with [OK], the
menu item "Units of measurement" will be displayed.
Units of measurement
bar
3 Activate the selection with [OK] and select the requested
unit with [–>] (in the example mbar).
4 Confirm with [OK] and move to position correction with
[–>].
The adjustment unit is now changed from bar to mbar.
Proceed as follows:
1 Edit the offset value in the menu item "Position correction"
with [OK].
Position correction
Offset =
P
+0000.0 mbar
53.0 mbar
2 Set the requested offset value, e.g. the actual measured
value with reciprocal sign with [–>] and [+].
3 Confirm with [OK] and move to min. (zero) adjustment with
Selection options: mbar, bar, psi, Pa, kPa, MPa, inHg, mmHg, inH
5)
mmH
O.
2
5)
VEGABAR 53 - Profibus PA
O,
2