Setup with the indicating and adjustment module PLICSCOM
Parameter adjust-
ment "Level meas-
urement"
26
Information:
To adjust with pressure, you simply enter the indicated actual
measured value. If the adjustment ranges are exceeded, the
message is displayed "Outside parameter limits". The editing
procedure can be interrupted with [ESC] or the displayed limit
value can be accepted with [OK].
The setup of VEGABAR 53 for process pressure measure-
ment is finished. All other menu items are described in the
separate operating instructions manual of the indicating and
adjustment module PLICSCOM.
Level measurement
Set up VEGABAR 53 in the following sequence:
1 Select application "Level measurement"
2 Select adjustment unit/density unit
3 Carry out position correction
4 Carrying out min. adjustment
5 Carrying out max. adjustment
In the menu item "Application" you switch over from "Process
pressure" to "Level measurement".
In the menu item "Units of measurement" you select the
physical unit in which the adjustment should be carried out, e.
g. mbar, bar, psi...
The position correction compensates the influence of the
mounting position or static pressure on the measurement. It
does not influence the adjustment values.
Information:
These steps are not necessary for instruments which are
already preset acc. to customer specifications!
You can find these data on the type label on the instrument and
in the menu items of the min./max. adjustment.
PLICSCOM enables the adjustment without filling or pressure.
You can carry out the settings in the workshop without the
instrument having to be installed.
Also the current measured value is shown in the menu items
for the min./max. adjustment.