Procedure
(continued)
Select Yes to
Enable Modem
3.4 Click on the Setup icon on the left side bar. The 61000 Setup page will be
displayed.
3.5 In the TCP/IP section, set the IP Address, Subnet Mask, and Gateway as
required for the LAN where the unit will be connected. Typically, the
Subnet mask is 255.255.255.0 and the Gateway is 0.0.0.0. Consult your
IT department for different configurations if required.
3.5 Specify the instrument to which the Serial port settings apply. Click on the
Used for down arrow to display the pull down menu and select Modem
(PPP).
3.6 Proceed to the PPP setup box and make sure it is Enabled. Click on the
Yes radio button.
The DataNode IP and Remote IP are left in their default settings. The PPP
Modem Init (initialization) string should also be left in its default setting
(which appears as a blank).
NOTE: Use a different modem initialization string if the modem requires
something specific.
3.7 When done setting up the 61000 for modem operation, press Submit
Changes at the bottom of page.
3.8 Disconnect the cross-over Ethernet cable from the instrument and the
computer. Connect the instrument to the LAN using the provided standard
Ethernet cable (usually grey cable).
3.9 Reconfigure the computer for normal operation on the LAN, which will
usually require restoring the original configurations modified in Step 2.1.
3.10 The 61000 can now be contacted using the Encore Series Software.
Chapter 4/ Operational Description
Continued on next page
Serial port
settings to be
used for Modem
4-11