Dranetz Encore Serirs 6100 System Installation Manual page 108

Table of Contents

Advertisement

Measurement Parameters, continued
Type: Voltage Pods
Voltage Pods
Connection:
Screw terminals (Model 5536 - part number 116850-G1)
Screw terminals (Model 5531 - part number 83004787-G2)
Input impedance: (Differential) 2 MΩ, minimum, Input to Ground
Impedance: (line to line) 4 MΩ
Installation Category: CAT III, Pollution Degree 2
Type: Current Pods
Current Pods
Ch 4 has TR connector to:
Current Pod - Model 5538
• Part No.: 116895-G1
• Nominal Rating: 5 Amps
• Overload: 5X
• No. of Turns: 1000
• Internal Burden: 121 Ω
• VA Burden at nominal input: 0.00303 VA
Screw Terminal connection to:
Current Pod - Model 5537
• Part No.: 116870-G1
• Nominal Rating: 5 Amps
• Overload: 5X
• No. of Turns: 1000
• Internal Burden: 121 Ω
• VA Burden at nominal input: 0.00303 VA
Screw Terminal connection to:
Current Pod - Model 5534
• Part No.: 116870-G2
• Nominal Rating: 1 Amps
• Overload: 5X
• No. of Turns: 1000
• Internal Burden: 750 Ω
• VA Burden at nominal input: 0.00075 VA
B-8