Rear Panel for 61SGD and 61SG Units - Switchgear Mounting Units
Rear panel
(continued)
The 61SGD and 61SGD monitor (henceforth referred to as 61SGD in this section) is
similar in functionality to the 61RMTD and 61RMT respectively, except that they are
designed to be mounted into a switchgear enclosure, rather than a 19" rack, and the
power supply inputs are different. All of the same input module options and
communication options of the 61STD and 61RMTD are applicable. The power supply
inputs are designed for 90-250Vac, 50/60Hz, or 105-125Vdc. A screw terminal strip is
used to connect the appropriate gauge wire for the application. The positive and
negative inputs are fused with user-replaceable fuses of the same type as provided with
the product. See below for description of the 61SGD rear panel as configured with
three modules.
Input Modules
See Input Module Connectors,
page 2-15 for a detailed description
of the input module connectors for
61SGD
Optional
Optional enclosures for 61STD, 61RMTD, 61RMT, 61SG, 61SGD, 61VENCL,
enclosures
61WENCL and 61VCM are available in Dranetz-BMI. See Appendix A Optional
Acessories - Enclosure Hardware Options for details.
Chapter 2/ Controls, Indicators, and Connectors
Communications Ports
See Communications Interface,
page 2-10 for a description of
the 61000 data ports
SF-203d
Power Input
See Connecting to 90-250Vac/
105-125Vdc Power Source,
page 2-7 on how to power the
unit on/off