To change any of the settings shown in Table 2-3, proceed as follows:
1. Turn the rotary switch to SETUP.
2. If the setting you want to change is not on the first Setup screen, press
$ Page Down to see additional Setup screens.
3. Use D U to highlight the setting you want to change.
4. Press ! Choice.
5. Use D U to highlight the setting you want.
6. Press E to store the highlighted setting.
7. Repeat steps 2 through 6 to change additional settings.

Results within Accuracy Range

An asterisk following a test result value indicates that the value is within the test
tool's range of accuracy, as shown in Figure 2-3. All tests except the wire map test
may produce results with an asterisk if required by the selected test standard. If
you want the asterisk to appear on the overall pass/fail test result as well as the
individual test result, enable "Top Level Pass* Indication" in SETUP.
If a "pass" result is marked with an asterisk, look for ways to improve the cabling
installation to eliminate the marginal performance. A "fail" result marked with an
asterisk should be considered a failure.
The asterisk appears on displayed, uploaded, and printed test results.
Pass
*
Pass Region
Fail
Figure 2-3. The Asterisk and Test Tool Accuracy
Limit
*
Fail Region
Getting Started
2
Quick Start
Accuracy
Range of
Test Tool
oy02f.eps
2-9