(c) Error handling
Confirm that the ERROR LED for the Q64RD is off. If the ERROR LED is lit,
click on Close , check the error code on the monitor screen, and then
perform the offset/gain settings again.
Perform operation in the following sequence to save/restore the user range.
(1) Switch to the Pass data screen
Perform the operation in Section 5.6.1 to display the pass data screen.
(2) User range saving
(a) Change the Setting value field of pass data read request to "Request", and
click the Execute test button.
When read is completed, the values are displayed in the Current value fields
of 3/4-wire type CH
wire type CH
CH
User range settings offset/gain set value.
(b) Compare the values with those in the range reference table, and record
them if they are correct.
Refer to Section 7.4 for the range reference table.
(3) User range restoration
(a) Set the recorded values in the Setting value fields of 3/4-wire type CH
Industrial shipment settings offset/gain input value/3/4-wire type CH
range settings offset/gain input value/3/4-wire type CH
offset/gain set value.